Get Instant Quote
Leave Your Message
PHD-12TF-277

Digital Input

Products Categories
Featured Products

PHD-12TF-277

Digital Input Isolated Safety Barrier 

PHD-12TF-277 1 input and 2 output

PHD-22TF-2727 2 input and 2 outputs

Input: Switch contacts/proximity switches

Output: Relay

    Overview

    The isolated safety barrier with switch input relay outputs, which isolates and transmits input signals from switch contacts or proximity switches in hazardous areas to of the safety zone with output relay through the safety barrier. Line fault detection is achieved through LED on the top of the module. The dial switch of the module is used to set input and output in-phase or reverse control, as well as to enable or disable the line fault detection alarm indication function.

     

    This product requires independent power supply, with isolated power supply, input, and output terminals.

     

     

    Specifications

     

     

    Specifications

     

    Input in harzadous area

     

    Input signal

    Switch contacts/proximity switches

    The supply voltage of the sensor

    About 8V

    Switching rate

    <10Hz

    Input/output characteristics:

     

    On site input current

    >2.1mA, the output is closed, indicating ON;
    When<1.2mA, the output is open circuit, indicating OFF

    Output normally "Open"/"Closed"

    Contact conversion control

    When dial switch K1, K3 is at "ON" side, the relay output is "Normally closed".

    When dial switch K1、K3 is at "OFF" side, the relay output is "Normally closed".
    When dial switch K2、K4 is at "ON" side, the circuit selects indicating red light LFD alarm function.

    Output in safe area

     

    Output signal

    Relay 

    Contact capacity

    250VAC/2A,30VDC/2A when subjected to resistive loads

    Response time

    20ms

    Basic parameters

     

    Supply voltage

    20~35VDC

    Power consumption

    24V power supply, when the relay contacts close
    <30mA(PHD-12TF-277) 
    <40mA(PHD-22TF-2727)

    LED indicator

    Green: Power indicator
    Yellow: Output relay in normal working state
    Red: LFD indication, line fault alarm

    Temperature parameters

    Working temperature: -20℃ ~ +60℃,
    Storage temperature: -40℃ ~ +80℃

    Relative humidity

    10%~95% RH no condensation

    Insulation strength

    Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)

    Insulation resistance

    ≥100MΩ (between input/output/power supply)

    Electromagnetic compatibility

    According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1

    MTBF

    100000h

    Wire requirements

    Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V

    Applicable field equipments

    Field equipment such as dry contacts or NAMUR type proximity switch inputs that comply with DIN19234 standard

    Installation place

    Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

    Intrinsically safe certification

     

    Functional safety certification

    SIL3 according to IEC 61508 standards

    Explosion proof mark

    [Ex ia Ga]lIC [Ex ia Da]lllC

    Explosion-proof standard

    GB/T3836.1-2021  GB/T3836.4-2021

    Terminals 3-4、1-2

    Um:250V AC/DC Uo=10.5V DC lo=15mA 
    Po=39.4mW Co=1.7μF Lo=165mH

    Certification body

    CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    PHD-12TF-2778m1

     

    Note: 

    1. PHD-12TF-277 does not include input part 2
    2. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.

    Line Fault Detection

    Users can select the "ON" side of the switch at the top of the module to enable fault detection function and indicate an alarm through the red LED light. On site input current>7mA, short circuit alarm (SC); On site input current<0.1mA, open circuit alarm (LB). If the switch contact input requires fault detection function (wire breakage, short circuit), a 22k Ω resistor should be connected in parallel at both ends of the switch, and a 680 Ω resistor should be connected in series (as shown in the wiring diagram for switch contact II).

     

     

    Terminal assignments and dimensions

     

     

    Terminal

    Terminal assignments

    9

    Power supply +

    2035VDC

    10

    Power supply -

    3

    Input+

    4

    Input-

    5

    Relay  output 1

    6

    Relay  output 1

    7

    Relay output 2

    8

    Relay output 2

     

    phd-2tf-277(1)332

     

    Product Display

     

     

    PHD-12TF-27790x
    PHD-12TF-2770u9