Get Instant Quote
Leave Your Message
PHL-S24-L2 24V Voltage System SPD

Not intrinsically safe

Products Categories
Featured Products

PHL-S24-L2 24V Voltage System SPD

Product overview

The PHL-S series SPD is designed specifically for protecting on-site equipment in control rooms, including transmitters, switches, frequency signals, communication equipment, TC, RTD, as well as I/O, DCS, PLC and other equipment. These devices are usually connected using two wire and three wire systems, and the use of SPD is necessary to prevent damage caused by lightning impulse voltage or over-voltage during operation.

    main features

    1.Top display with status alarm: SPD devices are equipped with top displays that can display the device's working status in real-time. This design allows users to timely understand the operation of the equipment in order to take necessary measures to protect the equipment and system.
    2.Ultra thin design with a thickness of only 7mm, saving space: The SPD device adopts an ultra-thin design with a thickness of only 7mm, which makes it occupy very little space during installation. In control room environments with limited space, this ultra-thin design can effectively save space and make installation more convenient.
    3.High bandwidth, low insertion loss, suitable for various signals: This series of SPDs has the characteristics of high bandwidth and low insertion loss, suitable for protection of various signal types. SPD can provide effective protection for both low-frequency and high-frequency signals, ensuring the stability and reliability of signal transmission.

    SPECIFICATIONS

    Technical data

    Two-wire

    Three-wire

    Product type

    PHL-S24-L2.5kA

    PHL-S24-L2.10kA

    PHL-S24-L3.5kA

    PHL-S24-L3.10kA

    Nominal discharge current In (8 / 20μs)

    5kA

    10kA

    5kA

    10kA

    The maximum discharge current (8 / 20μs)

    10kA

    20kA

    10kA

    20kA

    Lightning surge current limp (10 / 350μs)

    0.5kA

    2kA

    0.5kA

    2kA

    Total lightning surge current (10 / 350μs)

    1kA

    4kA

    1.5kA

    6kA

    Rated operating voltage Un

    24V

    24V

    Maximum operating voltage Uc

    32V

    32V

    Nominal operating current IL

    1A

    1A

    Protection voltage Up (8 / 20μs) line-to-line / line to ground

    60V / 600V

    60V / 600V

    Protection voltage Up (1KV / μs) line to line / line to ground

    60V / 600V

    60V / 600V

    Bandwidth (-0.5dB)

    10MHz

    10MHz

    Response time

    1ns

    1ns

    Series resistance (per line)

    Leakage current

    <10μA

    <10μA

    Degrees of protection provided by enclosure (in line with IEC 60529)

    IP 20

    IP 20

    Housing material / Flame retardant grade (the UL94)

    PC/V0

    PC/V0

    Test standard

    GB/T 18802.21 / IEC61643-21

    GB/T 18802.21 / IEC61643-21

    Working temperature range

    -40~+80℃

    -40~+80℃

    Overall dimension

    非本安24V yys

    diagram

    非本安24V-1 ghg

    Schematic diagram

    非本安24V-2 xxi