- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
0102030405
PHL-TX24-P4-*-EX Field Instrument Surge Protective Devices
Product Advantages
Technical data | Two-wire | Three-wire | Four-wire |
Rated operating voltage Un | 24V | 24V | 24V |
Maximum operating voltage Uc | 35V | 35V | 35V |
Nominal operating current IL | 10kA | 10kA | 10kA |
Nominal discharge current In (8 / 20μs) | 20kA | 20kA | 20kA |
Maximum discharge current (8 / 20μs) | 20kA | 20kA | 20kA |
Lightning surge current limp (10 / 350μs) | 2.5kA | 2.5kA | 2.5kA |
Total lightning surge current (10 / 350μs) | 5kA | 7.5kA | 10kA |
Protection voltage Up (8 / 20μs) line-to-line | 60V | 60V | 60V |
Protection voltage Up (1KV / μs) line to ground | 600V | 600V | 600V |
Response time | 1ns | 1ns | 1ns |
Degrees of protection provided by enclosure (in line with IEC 60529) | IP 67 | IP 67 | IP 67 |
Housing material | 304 Stainless steel | 304 Stainless steel | 304 Stainless steel |
Thread format | Specify when ordering | Specify when ordering | Specify when ordering |
Test standard | GB/T 18802.21 / IEC61643-21 | GB/T 18802.21 / IEC61643-21 | GB/T 18802.21 / IEC61643-21 |
Explosion-proof certifications | EX d II C T4-T6 Gb | EX d II C T4-T6 Gb | EX d II C T4-T6 Gb |
EX ia II C T4-T6 Ga | EX ia II C T4-T6 Ga | EX ia II C T4-T6 Ga | |
Working temperature range | —40 ℃ ~ +80 ℃ | —40 ℃ ~ +80 ℃ | —40 ℃ ~ +80 ℃ |
Diagram
The "*" in the model number represents the thread specification, which must be specified when ordering:
I:M20X1.5 N:1/2”NPT G:G1/2”
Schematic diagram
Dimension drawings
Note: The connecting rail specification is 15m², length is 250mm with multi-stranded wire, is resistant to acid
and abrasion.