PHD-22HZ-*1*1
measurement range
Code |
RTD model |
Measurement range |
Minimum range |
Conversion accuracy |
1 |
G53 |
-50~150℃ |
20℃ |
0.2℃/0.1% |
2 |
Cu50 |
-50~150℃ |
20℃ |
0.2℃/0.1% |
4 |
Pt100 |
-200~850℃ |
20℃ |
0.2℃/0.1% |
6 |
Pt1000 |
-200~850℃ |
20℃ |
0.2℃/0.1% |
7 |
Ni1000 |
-60~250℃ |
20℃ |
0.2℃/0.1% |
Specifications
Supply voltage |
20~35VDC, power consumption<2W (when power supply 24VDC, output 20mA) |
Input signal |
Two-wire or three-wire RTD |
Output signal |
4~20mA |
Signal and measurement range |
Signal range: corresponding to the measurement range of RTD Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained |
Allowable output load capacity |
0~500Ω (customizable) |
Alarm indication |
L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
Channel number of input and output |
2 inputs 2 outputs |
Applicable field devices |
2-wire or 3-wire RTD (G53, Cu50, Pt100, Pt1000, Ni1000) |
Output accuracy |
0.1%F.S (Typical value: 0.05%F.S) |
Temperature drift |
0.005%F.S/℃ |
Temperature parameters |
Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃ |
Relative humidity |
10%~95% RH no condensation |
Insulation strength |
Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min) |
Insulation resistance |
≥100MΩ (between input/output/power supply) |
External dimensions |
Thickness 15.8mm * width 104.8mm * high 116.1mm |
Electromagnetic compatibility |
According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark |
[Exia Ga]IIC |
Certification body |
CQST (China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters (between terminals 4-5-6.1-2-3) |
Um=250V Uo=8.4V Io=31mA Co=4.8μF Lo=20mH Po=65mW |
Installation site requirements |
It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF |
≤100000h |