- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
PHD-22TD-2121
Product Advantages
Isolated safety barrier at detection side: PHD-22TD-2121, dual input and dual output with analog signal.
The isolated barrier can isolate and transmit the 4~20mA signal or DC 4~20mA signal generated by the transmitter in the dangerous area to the safe area, the output signal is 4~20mA. When the transmitter is two-wire or three-wire system, the safety barrier
provides power for the transmitter.
This product needs an external 20~35VDC power supply.
* Bus power supply, please see appendix for details.
Specifications
Supply voltage |
20~35VDC, power consumption<2.8W (when supply power 24VDC, transmitter input, output 20mA) |
Power supply output with provided power |
When the circuit output is 20mA, the provided voltage is ≥16V |
Input signal |
two-wire or three-wire transmitter or current source signal (HART) |
Output signal |
4~20mA (HART) |
Allowable output load capacity |
0~500Ω(customizable) |
Output accuracy |
0.1%F.S(Typical values:0.05%F.S) |
Temperature drift |
0.005%F.S/℃ |
Number of input and output channels |
2 input 2 output |
Applicable field equipment |
2-wire, 3-wire transmitter and current source signal, this product is suitable for ABB, Fisher, Rosemount, Honeywell, as well as 3351, EJA, SIEMENS
and other products with imported technology.
|
Temperature parameters |
Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity |
10%~95% RH no condensation |
Insulation strength |
Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min) |
Insulation resistance |
≥100MΩ (between input/output/power supply) |
Dimensions |
Thickness 12.5mm* width 108mm* height 118mm |
Electromagnetic compatibility |
According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark |
[Exia Ga]IIC |
Functional safety certification |
SIL2 according to IEC 61508 and EN 61511 standards |
Certification Body |
CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters (Between terminals 1-2) |
Um=250V Uo=3.5V Io=—mA Co=100μF Lo=—mH Po=—W |
Certified parameters (Between terminals 3-4) |
Um=250V Uo=28V Io=93mA Co=0.05μF Lo=2.4mH Po=0.65W |
Installation site Requirements |
It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF |
≤100000h |
Wiring diagram
Terminal assignments and dimensions
Terminal
Terminal assignments
14
Power supply +
20~35VDC
15
Power supply -
2-wire
3-wire
Current source
5
Input1+
Provided power supply1+
4
Input1-
Input1-
6
Input1-
Input1+
Input1+
2
Input2+
Provided power supply2+
1
Input2-
Input2-
3
Input2-
Input2+
Input2+
8
Output1 +
4~20mA
9
Output 1-
11
Output2+
4~20mA
12
Output2 -
Terminal | Terminal assignments | ||
14 | Power supply + | 20~35VDC | |
15 | Power supply - | ||
2-wire | 3-wire | Current source | |
5 | Input1+ | Provided power supply1+ | |
4 | Input1- | Input1- | |
6 | Input1- | Input1+ | Input1+ |
2 | Input2+ | Provided power supply2+ | |
1 | Input2- | Input2- | |
3 | Input2- | Input2+ | Input2+ |
8 | Output1 + | 4~20mA | |
9 | Output 1- | ||
11 | Output2+ | 4~20mA | |
12 | Output2 - |