Get Instant Quote
Leave Your Message
PHD-11TD-21

Analog Input

Products Categories
Featured Products

PHD-11TD-21

Overview

Isolated safety barrier at detection side: PHD-11TD-21, analog input and output, single input and single output.

^ The isolated barrier can isolate and transmit the 4~20mA signal or DC 4 ~ 20 mA signal generated by the transmitter in the dangerous area to the safe area. When the transmitter is two-wire or three-wire system, the safety barrier provides power for the transmitter.

^ This product needs an external 20-35VDC power supply.

^ This product supports HART signal and disconnection alarm.

* Note: If you need other parameters of this product, please contact our technical support. If the output is other parameters, it is indicated by the number 9, and the specific parameters are indicated after the model number.

^ Example: input 2-wire, 3-wire or 4-20mA, output 2~10V.

^ Model: PHD-11TD-29 (2-10V)

* Bus power supply, see appendix for details.

    Product Specifications

    Supply voltage 20~35VDC, power consumption<1.5W (when supply power 24VDC, transmitter input, output 20mA)
    Power supply output with provided power When the circuit output is 20mA, the provided voltage is ≥ 16V
    Input signal Two-wire or three-wire transmitter or current source signal (HART)
    Output signal 4~20mA (HART)
    Allowable output load capacity 0~500Ω(customizable)
    Output accuracy 0.1%F.S(Typical value:0.05% F.S)
    Temperature drift 0.005% F.S/℃
    Number of input and output 1 input 1 output
    Applicable field equipment 2-wire, 3-wire transmitter and current source signal, this product is suitable for ABB, Fisher, Rosemount, Honeywell 11, as well as 3351, EJA, SIEMENS and other products with imported technology.
    Temperature parameters Working temperature: -20℃ ~ +60℃, storage temperature: -40℃ ~ +80℃
    Relative humidity 10%~95% RH no condensation
    Insulation strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    Dimensions Thickness 12.5mm* width 108mm* height 118mm
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga] IIC
    Functional safety certification SIL2 according to IEC 61508 and EN 61511 standards
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 1-2) Um=250V  Uo=3.5V  Io=—mA  Co=100μF  Lo=--mH  Po=--W
    Certified parameters (between terminals 3-4) Um=250V  Uo=28V  Io=93mA  Co=0.05μF  Lo=2.4mH  Po=0.65W
    Installation place requirements It can be connected with instruments in 0 zone with IIA, IIB, IIC dangerous gas
    MTBF ≤100000h

    Wiring diagram

    PHD11TD21tcn
    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply + 20~35VDC

    10

    Power supply -
      2-wire 3-wire Current source

    1

        Input+

    2

      Input- Input-

    3

    Input+ Provided power supply+  

    4

    Input- Input+  

    5

    Output+ 4~20mA

    6

    Output-
    PHD11TD21-16pp

    product display

    • Isolated Safety Barrier at Detection Side (5)bpi
    • Isolated Safety Barrier at Detection Side (4)o4b