- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
PHD-12TT-*11
Product Advantages
parameter
Input signal types and measurement range | ||||
Code |
TC model |
Measurement range |
Minimum range |
Conversion accuracy |
1 |
K |
-200~1370℃ |
50℃ |
0.5℃/0.1% |
2 |
S |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
3 |
E |
-140~1000℃ |
50℃ |
0.5℃/0.1% |
4 |
J |
-160~1200℃ |
50℃ |
0.5℃/0.1% |
5 |
B |
250~1800℃ |
500℃ |
1.5℃/0.1% |
6 |
T |
-200~400℃ |
50℃ |
0.5℃/0.1% |
7 |
R |
-50~1760℃ |
500℃ |
1.5℃/0.1% |
8 |
N |
-200~1300℃ |
50℃ |
0.5℃/0.1% |
Wiring diagram
Terminal assignments and dimensions
Terminal |
Terminal assignments |
|
9 |
Power supply + |
20~35VDC |
10 |
Power supply - |
|
3 |
Input+ |
TC |
4 |
Input- |
|
5 |
Output 1+ |
4~20mA |
6 |
Output 1- |
|
7 |
Output 2+ |
4~20mA |
8 |
Output 2- |
Specifications
Input signal |
K, S, E, J, B, T, R, N, TC Signals |
Output signal |
4~20mA |
Signal and measurement range |
Signal range: corresponding to the measuring range of TC -10~100mV |
Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained. | |
Allowable output load capacity |
0~500Ω(customizable) |
Alarm indication |
L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
Channel number of input and output |
1 input 2 outputs |
Applicable field devices |
K, S, E, J, B, T, R, N TC sensors |
Output accuracy |
0.1%F.S (Typical value: 0.05%F.S) |
Cold junction compensation |
±1℃ (Compensation range -20℃-+60℃) |
Temperature drift |
0.005%F.S/℃ |
Temperature parameters |
Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
Relative humidity |
10%~95% RH no condensation |
Dielectric strength |
Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
Insulation resistance |
≥100MΩ (between input/output/power supply) |
External dimensions |
Thickness 12.5mm x width 108mm x high 118mm |
Electromagnetic compatibility |
According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
Explosion-proof mark |
[Exia Ga]IIC |
Certification Body |
CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
Certified parameters (between terminals 3-4) |
Um=250V Uo=8.4V Io=31mA Co=4.8μF Lo=20mH Po=65mW |
Installation site Requirements |
It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas |
MTBF |
≤100000h |