Get Instant Quote
Leave Your Message
PHD-12TD-211

Analog Input

Products Categories
Featured Products

PHD-12TD-211

PHD-12TD-211

Two or three-wire transmitter or current source input /4~20mA output 1 input 2 output


Overview

PHD-12TD-211 is an isolated detection end safety barrier designed specifically for analog input and output.

    Product Advantages

    1.Analog input/output: Supports analog input and output, can process 4-20mA signals or DC 4-20mA signals, and isolate and transmit them to a safe area. The output signal is 4-20mA.
    2.Input and output channels: one input and two outputs, which can flexibly meet different signal transmission needs.
    3.Isolation function: To achieve electrical isolation between input and output, ensuring the stability and safety of signal transmission.
    4.Power supply function: When the on-site transmitter is a two or three wire system, the safety barrier can provide power distribution for the transmitter to ensure its normal operation.
    5.External power supply: An external 20-35VDC power supply is required to provide sufficient power support.
    6.Support for Hart signal: Compatible with Hart signal, suitable for application scenarios that require support for the Hart communication protocol.

    * Bus power supply, see appendix for details.

    Specifications

    Supply voltage

    20~35VDC,power consumption<2W(when  supply power 24VDC, transmitter input, output 20mA)

    Power supply output with provided power

    When the circuit outputs is 20mA, the provided voltage is ≥ 16V

    Input signal

    two-wire or three-wire transmitter or current source signal (HART)

    Output signal

    4~20mA  (HART)

    Allowable output load capacity

    0~500Ω(customizable)

    Output accuracy

    0.1%F.S(Typical values:0.05%F.S)

    Temperature drift

    0.005%F.S/℃

    Number of input and output channels

    1 input 2 output

    Applicable field equipment

    2-wire,3-wire transmitter and current source signal, this product is suitable for ABB, Fisher, Rosemount, Honeywell 11, and 3351, EJA, SIEMENS and other products with imported technology.

    Temperature parameters

    Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃

    Relative humidity

    10%~95% RH no condensation

    Insulation strength

    Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)

    Insulation resistance

    ≥100MΩ (between input/output/power supply)

    Dimensions

    Thickness 12.5mm* width 108mm* height 118mm

    Electromagnetic compatibility

    According to IEC 61326-1(GB/T 18268), IEC 61326-3-1

    Explosion-proof mark

    [Exia Ga]IIC

    Functional safety certification

    SIL2 according to IEC 61508 and EN 61511 standards

    Certification Body

    CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

    Certified parameters (Between terminals 1-2)

    Um=250V  Uo=3.5V  Io=—mA  Co=100μF  Lo=—mH  Po=—W

    Certified parameters (Between terminals 3-4)

    Um=250V  Uo=28V  Io=93mA  Co=0.05μF  Lo=2.4mH  Po=0.65W

    Installation site Requirements

    It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas

    MTBF

    ≤100000h

    Wiring diagram

    PHD12211bm0

    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply +

    20~35VDC

    10

    Power supply -

     

    2-wire

    3-wire

    Current sourc

    1

       

    Input+

    2

     

    Input-

    Input-

    3

    Input+

    Provided power supply+

     

    4

    Input-

    Input+

     

    5

    Output 1+

    4~20mA

    6

    Output 1-

    7

    Output 2+

    4~20mA

    8

    Output 2-

    12211b2i

    Application scenario

    ◔ Industrial safety monitoring: A safety monitoring system used in the industrial field, such as chemical plants, petrochemicals, pharmaceuticals, and other fields.
    ◔ Process control: Used for signal isolation and transmission in process control systems, such as monitoring and controlling parameters such as temperature, pressure, and liquid level.
    ◔ Safe isolation: used in situations where signal isolation is required for hazardous and safe areas, to ensure safe operation and production.
    ◔ Remote monitoring: used for signal transmission and isolation in remote monitoring systems, such as remote monitoring stations, data acquisition systems, etc.

    product display

    • Isolated Safety Barrier at Detection Side (4)d07
    • Isolated Safety Barrier at Detection Side (5)0g9