Get Instant Quote
Leave Your Message
PH6001-1A Intelligent safety relay

SIS System Safety Relays

Products Categories
Featured Products

PH6001-1A Intelligent safety relay

PH6001-1A is a safety relay control module, which is suitable for DI/DO signal isolation conversion in SIS system. It has one normally open (NO) contact, and the reserved terminal is convenient for fast off-line Proof Test. The internal circuit adopts Fail-safe technology, triple redundancy technology and contact welding protection technology.

    Technical data

    Technical data
    Power supply characteristics
    Power supply 24V DC
    Current loss ≤35mA(24V DC)
    Voltage range 16V~35V DC nonpolarity
    Input characteristics
    Input current ≤ 35mA (24V DC)
    Wire resistance ≤ 15 Ω
    Input device SIS system DI/DO signal matching
    Output characteristics
    Number of contacts 1NO
    Contact material AgSnO2
    Contact fuse protection 5A (internal fuse blown protection)
    Contact capacity 5A/250V AC; 5A/24V DC
    Mechanical lifespan more than 107 times
    Time characteristics
    Switch-on delay ≤ 30ms
    Delay-on de-energisation ≤ 30ms
    Recovery time ≤ 30ms
    Supply short interruption 20ms

     

    safety certification
    Safety Integrity Level (SIL)  SIL3 conforms to IEC 61508
    Hardware Fault Tolerance(HFT) 0 conforms to IEC 61508
    Safe failure fraction(SFF)   99%  conforms to IEC 61508
    Probability of hazardous failure (PFHd)  1.00E-09 /h      conforms to IEC 61508
    StopCategory  0   conforms to EN 60204-1
    10% average number of hazardous failure cycles of components (B10d)
    Rated Voltage 24VDC, L/R=7ms  Ie         2A          1A         0.5A
    Cycles 180,000  300,000  400,000
    Rated Voltage 230VAC , cos φ= 0.4 Ie           2A          1A            0.5A
    Cycles   500,000   580,000    600,000

     

    Environmental characteristics
    Electromagnetic compatibility conform to EN 60947,EN 61000-6-2,EN 61000-6-4
    Vibration frequency 10Hz~55Hz
    Vibration amplitude 0.35mm
    Ambient temperature -20 ℃~+60 ℃
    Storage temperature -40 ℃~+85 ℃
    Relative humidity 10% to 90%
    Altitude ≤ 2000m

     

    Insulation characteristics
    Electrical clearance and creepage distance conform to EN 60947-1
    Overvoltage level III
    Pollution level 2
    Protection level IP20
    Insulation strength 1500V AC, 1 minute
    Rated insulation voltage 250V AC
    Rated impulse voltage 6000V (1.2/50us)

     

    External dimensions

    1d65

     

    Block diagram

    2b1r

     

    Wiring diagram

    3wsd

    (1) The instrument wiring adopts Pluggable connecting terminal ;
    (2) The soft copper cross-sectional area of the input side wire must be greater than 0.5mm2, and the output side must be greater than 1mm2;
    (3) The exposed length of the wire is about 8mm, which is locked by M3 screws;
    (4) The output contacts must provide enough fuse protection connections;
    (5) Copper conductor must withstand an ambient temperature of at least 75 ℃; 
    (6) Terminal screws can cause misoperation, heating, etc. Therefore, please tighten it according to the specified torque. Terminal screw tightening torque 0.5Nm.

    wiringrps

    Installation

    Safety relays should be installed in control cabinets with at least IP54 protection level.
    The PH6001-1A series safety relays are all installed with DIN35mm guide rails. Installation steps are as follows
    (1) Clamp the upper end of the instrument onto the guide rail;  
    (2) Push the lower end of the instrument into the guide rail.

    installdxn

    Dismantling

    Insert a screwdriver (blade width ≤ 6mm) into the metal latch at the lower end of the instrument panel;
    Push the screwdriver upwards and pry the metal latch downwards;
    Pull the instrument panel up and out of the guide rail.

    disassehaa

    Attention

    Please verify whether the product packaging, product label model, and specifications are consistent with the purchase contract;
    Before installing and using safety relays, carefully read this manual;
    If you have any questions, please contact the Beijing Pinghe Technical Support Hotline at 400 711 6763;
    The safety relay should be installed in a control cabinet with at least IP54 protection level;
    The instrument is powered by 24V  power supply, and the use of 220V AC power supply is strictly prohibited;

     

    Maintenance

    (1) Please regularly check whether the safety function of the safety relay is in good condition, and whether there are signs that the circuit or the original is tampered with or bypassed;
    (2) Please follow the relevant safety regulations and operate according to the instructions in this instruction manual, otherwise it may lead to fatal accidents or loss of personnel and property;
    (3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the products are not working properly and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline.
    (4) Within six years from the date of delivery, all product quality problems during normal use shall be repaired by Pinghe free of charge.