Get Instant Quote
Leave Your Message
PHC-11TD-11+

Digital Output

Products Categories
Featured Products

PHC-11TD-11+

Analogue Output Isolated Safety Barrier with surge protection function

 input and 1 output

Input: 4~20mA (HART digital signal)
Output: 4~20mA (HART digital signal)

    Overview

    The analog output isolated safety barrier with surge protection function can realize the isolated transmission of 4~20mA signals from the instruments in the safe area to the dangerous area, drive the valve positioner, electric/pneumatic converter and other equipment on site, and support the bidirectional transmission of HART digital signals with wirebreak alarm function. This product needs independent power supply, and the power supply, input and output are isolated.

    Specifications

    Input insafe area
    Input signal  4~20mA (HART digital signal)
    Output in dangerous area
    Output signal 4~20 mA(HART  digital signal)
    Load resistance When outputting 20mA, 0~500 Ω (customizable)
    Nominal discharge current ln(8/20μs) 5kA
    Voltage protection level Up(8/20μs): 60V(line to line)
    Voltage protection level Up(8/20μs): 600V(line to ground)
    According to standards GB/T18802.21-2016(equivalent to 1EC61643-21:2012)
    Basic parameters
    Supply voltage 20~35VDC
    Power consumption ≤50mA(24V power supply, 20mA output)
    LED indicator  Green: power indicator
    Output accuracy 0.1%FS (Typical value: 0.05%F.S)
    Response time 2ms to reach 90% of the final value
    Temperature drift 0.005% F.S/℃
    Temperature parameters Working temperature: -20℃ ~ +60℃,
    Storage temperature: -40℃ ~ +80℃
    Relative humidity 10%~95% RH no condensation
    Insulation strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe side (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    MTBF 100000h
    Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
    Applicable field equipments Valve locator, electric/pneumatic converter
    Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
    Intrinsically safe certification
    Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
    Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
    Terminals 3-4 Um:250V AC/DC Uo=28V DC lo=93mA
    Po=0.65W Co=0.083μF Lo=4.2mH
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Shanghai lightning protection products testing center

     

    Dimension 

    PHC-11TD-11+.jpg

    Schematic Drawings

    PHC-11TD-11+(1).jpg

     

    Note: 
    1. The power supply of the power rail is an optional function. Users need to specify the power supply mode when ordering. Please refer to attachment on page 89.