Digital Input

Products Categories
Featured Products

PHD-22TF-2727

Switch or NAMUR proximity detector input /relay output

2 inputs 2 outputs

 

    Product Specifications

    Isolated safety barrier at detection side: PHD-22TF-2727, digital input and output, dual input and dual output.

    The isolated barrier can convert the proximity switch and contact input in the dangerous area  to the relay contact signal and transmit it to the safe area.

    The output relay is equipped with selection switch of  "ON/OFF" situation. In addition, there is an input signal short-circuit or open-circuit alarm indication, the circuit provides power for the input sensor.

    This product needs an external 20-35VDC power supply.

    The signal status indicator is set in red and yellow light to indicate the working status of the output relay, when it s for alarming then the light is red,  during normal operation the light is yellow.

    * Bus power supply, please see appendix for details.

    Product Specification




    Supply voltage 20~35VDC, power consumption<1.5W
    Input signal Switch contact/proximity switch
    Supply voltage from sensor side on site 8V
    Signal input characteristics
    On-site input current: >2.1mA, it means ON; on-site input current: <1.2mA, it means OFF  
    Switch hysteresis: 0.2ms
    Relay output characteristics Response time: 20ms, driving capacity: 250VAC/2A, 30VDC/2A under resistive load.
    Output "ON"/"OFF" contact conversion control
    When the dial switch K1, K3 is at "ON" side, the relay output is "OFF".
    When the dial switch K1, K3 is at "OFF" side, the relay output is "ON".
    When the dial switch K2, K4 is at "ON" side, the circuit selects indicating red light relay alarm function.
    Indicating light alarm function
    On-site input current > 7mA, short-circuit alarm (SC), on-site input current < 0.1mA, open-circuit alarm( LB)
    For switch contact input, when the disconnection detection function is required, a 10KΩ resistor must be connected parallel at both ends of the switch (Please see the switch contact II in the below wiring diagram)
    Number of input and output 2 input 2 output
    Applicable field equipments Dry contact or NAMUR proximity switch in accordance with DIN 19234 standard.
    Temperature parameter Working temperature: -20℃- +60℃, storage temperature: -40℃- +80℃
    Relative air humidity 10%~95%RH without condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    External dimensions Thickness 12.5mm x width 108mm x high 118mm 
    Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC
    Functional safety certification SIL3 according to IEC 61508 EN 61511 standards
    Certification Body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 3-4,1-2) Um=250V  Uo=10.5V  Io=15mA  Co=1.7μF  Lo=150mH  Po=39.4mW
    Installation site Requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
    MTBF ≤100000h

    PHD-22TF-2727(1)ked
    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply +

    2035VDC

    10

    Power supply -

    3

    Input 1+

    4

    Input 1-

    1

    Input 2+

    2

    Input 2-

    5

    Relay output 1

    6

    Relay output 1

    7

    Relay output 2

    8

    Relay output 2

    phd-22tf-2727(1)dj5