Get Instant Quote
Leave Your Message
PHD-22TT-*1*1

Temperature input

Products Categories
Featured Products

PHD-22TT-*1*1

TC input isolated safety barrier

PHD-22TT-*1*1  2 inputs 2 outputs

TC input/4~20mA output (configurable)

    Overview

    Thermocouple input isolation safety barrier can isolate and convert thermocouple (TC) signals in hazardous areas into 4-20mA current signals, and output them to the safety zone. This safety barrier has built-in cold end compensation and can be intelligently configured. The actual range of the thermocouple can be set through computer software. It has the functions of wire breakage alarm and out of range alarm.It has the functions of disconnection alarm and out-of-range alarm.

    This product requires independent power supply, with isolated power supply, input, and output terminals.

    "*" represents the input type of the thermocouple, and the specific model is represented by a code (see "Input Signal Type and Range Table" for details).

     

    Input signal types and measurement range

    Code

    TC model

    Measurement range

    Minimum range

    Conversion accuracy

    1

    K

    -200~1370℃

    50℃

    0.5℃/0.1%

    2

    S

    -50~1760℃

    500℃

    1.5℃/0.1%

    3

    E

    -140~1000℃

    50℃

    0.5℃/0.1%

    4

    J

    -160~1200℃

    50℃

    0.5℃/0.1%

    5

    B

    250~1800℃

    500℃

    1.5℃/0.1%

    6

    T

    -200~400℃

    50℃

    0.5℃/0.1%

    7

    R

    -50~1760℃

    500℃

    1.5℃/0.1%

    8

    N

    -200~1300℃

    50℃

    0.5℃/0.1%

    Example: when the input are 2 inputs with K-couple, temperature range is 0~1200℃, 2 outputs 4~20mA, power supply 20~35VDC, then the model should be PHD-22TT-1111 (0~1200℃).

    The measuring range can be set to the specified 0~1200℃ range by computer.

    * Bus terminal power supply, please see appendix for details.

     

    Specification

    Input in harzadous area

     

    Input signal

    K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Type and Range Table" for details)

    Input disconnection

    The default "low alarm" can be modified to "high alarm" through configuration software

    Signal range

    The measuring range of the corresponding thermocouple is -10~100mV.

    Measurement range

    Users make their own configuration when ordering, and indicate it at the tail number or otherwise.

    Built-in cold compensation

    ±1°C(Compensation range -20°C~ +60°C)

    Safety side output:

     

    Output signal

    4~20mA

    Output load capacity

    0~500Ω(customizable)
    Optional voltage output type, load resistance RL ≥ 330kΩ

    LED indicator

    Green: Power indicator
    Low range alarm yellow light on, high range alarm red light on

    Output accuracy

    Please refer to the "Input Signal Type and Range Table" for details

    Response time

    Reaching 90% of the final value within 500ms

    Temperature drift

    0.005%F.S/℃

    Temperature parameters

    Working temperature: -20~+60, storage temperature:-40~+80

    Relative humidity

    10%~95% RH no condensation

    Dielectric strength

    Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
    between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)

    Insulation resistance

    ≥100MΩ (between input/output/power supply)

    Electromagnetic compatibility

    According to IEC 61326-1(GB/T 18268), IEC 61326-3-1

    MTBF

    100000h

    Wire requirements

    Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V

    Applicable field equipments

    K. S, E, J, B, T, R, N TC sensors

    Installation place

    Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

    Intrinsically safe certification

     

    Functional safety certification

    SIL3 according to IEC 61508 standards

    Explosion proof mark

    [Ex ia Ga]lIC [Ex ia Da]lllC

    Explosion-proof standard

    GB/T3836.1-2021  GB/T3836.4-2021

    Terminals 3-24-2

    Um:250V AC/DC Uo=8.4V DC lo=31mA
    Po=65.1mW Co=4.8μF Lo=20mH

    Certification body

    CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

     

    Schematic diagram

    phd-22tcbm

    Note:

    1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

     

    The selection of power rail connectors can refer to page 89 of the "Annex"

     

    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply +

    2035VDC

    10

    Power supply -

    3

    Input 1+

    TC

    4

    Input 1-

    1

    Input 2+

    TC

    2

    Input 2-

     

        5

    Output 1+

    4~20mA

        6

    Output 1-

    7

    Output 2+

    4~20mA

    8

    Output 2-

     

    phd-22togg

     

    Product Display

    PHD-11TF-28ysk