Get Instant Quote
Leave Your Message
PHG-11TC-33M

Communication Input

Products Categories
Featured Products

PHG-11TC-33M

Communication signal input signal isolators

1 input 1 output

Input :RS-485 Half Duplex Digital Signal

Output :RS-485 Half Duplex Digital Signal

    Overview

    The PHG-11TC-33M is signal isolator with communication signal , which can realize the two-way communication of  RS-485 Half Duplex digital signal in the onsite and control room. The circuit provides power distribution for on-site instruments. The voltage value can be switched through the top dial switch. The specific operation method is shown in the chart below.
    This product needs independent power supply, and the power supply, input and output are isolated.

    PHG-11TC-33M(2).jpg

    Specifications

    Input
    Input signal RS-485 Half Duplex Digital Signal
    Distribution voltage Provide power distribution for field instruments: 5V, 6V, 12V, 24V
    Output:
    Output signal RS-485 Half Duplex Digital Signal
    Transmission delay  ≤10μs
    Transmission rate  ≤1.2kbps~56kbps
    Supply voltage 20-35VDC
    Power consumption <3.6W (24V power supply, 6V/100mA power distribution)
    LED indicator  Green: Power indicator
    Yellow: The control room transmits signals to the site
    Red: transmitting signals from the site to the control room
    Receiving and transmitting switching time  ≥20ms
    Temperature parameters Working temperature: -20℃~+60℃
    storage temperature:-40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength ≥2000VAC/min(between input/output/power supply)
    Insulation resistance 100MΩ(500 VDC) (between input/output/power supply)
    Electromagnetic compatibility GB/T 18268(IEC 61326-1)
    MTBF 800000h
    Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
    Applicable field equipments Communication interface device with RS-485 Half Duplex Digital Signal

    Dimension

    PHG-11TC-33M.jpg

    Schematic diagram

    PHG-11TC-33M(1).jpg

    Note:

    1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

    The selection of power rail connectors can refer to page 89 of the "Annex"