Get Instant Quote
Leave Your Message
PHG-11TT-*8+

RTD Signal

Products Categories
Featured Products

PHG-11TT-*8+

Surge protection type TC input temperature converter 

PHG-11TT-*8+  1 input 1 output

Input :TC signal

Output :1:1 millivolt signal

    Overview

    The   PHG-11TT-*8+ thermocouple input temperature converter with surge protection function can transmit the millivolt signal from thermocouple (TC) and output in 1: 1.

    This product requires independent power supply, with isolated power supply, input, and output terminals.

    "*" represents the input type of the thermocouple, and the specific model is represented by a code (see "Input Signal Type and Range Table" for details).

    Input signal types and measurement range
    Code TC model Measurement range Minimum range Conversion accuracy
    1 K -200~1370℃ 50℃ 0.5℃/0.1%
    2 S -50~1760℃ 500℃ 1.5℃/0.1%
    3 E -140~1000℃ 50℃ 0.5℃/0.1%
    4 J -160~1200℃ 50℃ 0.5℃/0.1%
    5 B 250~1800℃ 500℃ 1.5℃/0.1%
    6 T -200~400℃ 50℃ 0.5℃/0.1%
    7 R -50~1760℃ 500℃ 1.5℃/0.1%
    8 N -200~1300℃ 50℃ 0.5℃/0.1%

    For example: one input and one output, thermocouple K (-200~1370C) input, one channel 1:1 output, 24V power supply, model: PHG-11TT-18

    Specifications

    Input
    Input signal K, S, E, J, B, T, R, N thermocouple signals (see "Input Signal Type and Range Table" for details)
    Signal range The measuring range of the corresponding thermocouple is -5~60mV.
    Safety side output:
    Output signal Thermocouple 1: 1
    Surge protection features:
    Nominal discharge current ln(8/20μs) 5kA
    Voltage protection level Up(8/20μs): 60V(line to line)
    Voltage protection level Up(8/20μs): 600V(line to ground)
    According to standards GB/T18802.21-2016(equivalent to 1EC61643-21:2012)
    Power consumption <0.8W (24VDC power supply, 20mA output)
    LED indicator Green: Power indicator
    Output accuracy Please refer to the "Input Signal Type and Range Table" for details
    Response time Reaching 90% of the final value within 300ms
    Temperature drift 0.005%F.S/℃
    Temperature parameters Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Insulation strength ≥2000VAC/min  (between input/output/power supply)
    Insulation resistance 100MΩ(500V DC)   (between input/output/power supply)
    Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
    MTBF 80000h
    Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
    Applicable field equipments K. S, E, J, B, T, R, N TC sensors
    Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

    Dimension

    PHG-11TT-x8+.jpg

     Schematic diagram

    PHG-11TT-x8+(1).jpg

    Note:

    1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

    The selection of power rail connectors can refer to page 89 of the "Annex"