Get Instant Quote
Leave Your Message
PHG-11TZ Series

RTD Signal

Products Categories
Featured Products

PHG-11TZ Series

RTD signal input/DC signal output
1 input 1 output

    Overview

    RTD signal input, DC signal output, single input and signal output.
    Intelligently programmable, the actual measuring range of RTD can be set by computer.
    In the "Common models and parameters" the number "8" means "customizable".

    Specifications

    RTD excitation current

    800uA

    Load capacity 

    Current type load resistance≤500Ω, voltage type load current<5mA

    Output accuracy

     0.1%F.S

    Temperature drift

    0.005% F.S/℃

    Temperature parameters 

    Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃

    Relative humidity 

    10%~95% RH no condensation

    Insulation resistance 

    Between input and output, between input, output and power supply≥100MΩ (500VDC)

    Dielectric strength 

    Between input and output, between input, output and power supply≥2000VAC/min

    Electromagnetic                  compatibility

    GB/T 18268(IEC 61326-1)

    Power supply

    24VDC±10%

    Response time

     <100ms

    Power consumption 

    Current output<0.8W, voltage output<0.6W

    MTBF

    80000(h)

     

    Dimensions

    phg-11tov8

     

    Schematic diagram and terminal assignments

    phg-11tv6t

    Note: 1. When it is with three-wire RTD input, it is necessary to ensure that three wires are equal in length as much as possible.
    2. When it is with two-wire RTD input, the terminals 2 and 4 must be short-circuited connected.

    Terminal

    Terminal assignments

    9

    Power supply +

    24VDC±10%

    10

    Power supply -

     

    2-wire

    3-wire

     

    2

    Short connected with terminal 4

    Input-

     

    RTD signal

    3

    Input+

    Input+

    4

    Input-

    Input-

    5

    Output+

     

    DC signal

    6

    Output-

     

    Model definition

    phg-11tg4n

     

    Input signal type and range table

    Code

    RTD model

    Measurement range

    Minimum range

    Conversion accuracy

    1

    G53

    -50~150℃

    20℃

    0.2℃/0.1%

    2

    Cu50

    -50~150℃

    20℃

    0.2℃/0.1%

    4

    Pt100

    -200~850℃

    20℃

    0.2℃/0.1%

    6

    Pt1000

    -200~850℃

    20℃

    0.2℃/0.1%

    7

    Ni1000

    -60~250℃

    20℃

    0.2℃/0.1%

     

    Common models and parameters

    Model

    Channel numbers

    Input

    Output

    Power supply condition

    PHG-11TZ-41

    1 input 1 output

    Pt100(-200~850℃)

    4~20mA

    24VDC

    PHG-11TZ-42

    1 input 1 output

    Pt100(-200~850℃)

    0~20mA

    24VDC

    PHG-11TZ-43

    1 input 1 output

    Pt100(-200~850℃)

    0~5V

    24VDC

    PHG-11TZ-44

    1 input 1 output

    Pt100(-200~850℃)

    0~10V

    24VDC

    PHG-11TZ-45

    1 input 1 output

    Pt100(-200~850℃)

    1~5V

    24VDC

    PHG-11TZ-46

    1 input 1 output

    Pt100(-200~850℃)

    1:1

    24VDC

    PHG-11TZ-47

    1 input 1 output

    Pt100(-200~850℃)

    ±10V

    24VDC

    PHG-11TZ-11

    1 input 1 output

    G53(-50~150℃)

    4~20mA

    24VDC

    PHG-11TZ-21

    1 input 1 output

    Cu50(-50~150℃)

    4~20mA

    24VDC

    PHG-11TZ-61

    1 input 1 output

    Pt1000(-200~850℃)

    4~20mA

    24VDC

    PHG-11TZ-71

    1 input 1 output

    Ni1000(-60~250℃)

    4~20mA

    24VDC

    PHG-11TZ-88

    1 input 1 output

    Customizable

    Customizable

    24VDC

    Note: When make an order, please indicate the actual measured temperature range after the product model.