Get Instant Quote
Leave Your Message
PHL-S.Ex series

Other

Products Categories
Featured Products

PHL-S.Ex series

Intrinsically  Surge Protective Devices SPD

PHL-S.Ex series

    Overview

    PHL-S.Ex series SPD is mainly used to protect transmitters, switches, frequency signals, communication equipment, thermal resistors, thermocouples and other field devices connected in two-wire or three-wire mode, as well as control room I/O, DCS, PLC and other devices, so as to prevent them from being damaged by lightning surge impulse voltage or operating overvoltage.

    The main features are:

    1. With status alarm display function on top
    2. 7mm ultra-thin, saving space
    3. high bandwidth, suitable for all kinds of signals,

    Main technical parameters

    Parameter PHL-S5-L2 Ex
    PHL-S5-L3 Ex
    PHL-S24-L2 Ex
    PHL-S24-L3 Ex
    Rated operational voltage 5VDC 24VDC
    Maximum operating voltage Uc 6VDC 32VDC
    Rated operating current  IL 600mA 600mA
    Via resistance 1Ω/wire 1Ω/wire
    Bandwidth (-0.5dB) lOMHZ 10MHZ
    Response time 1 ns 1 ns
    Leakage current <10uA <10uA
    Nominal discharge current In (8 / 20μs) 5KA 10KA 5KA 10KA
    The maximum discharge current Imax (8 / 20μs) 10KA 20KA 10KA 20KA
    Lightning surge current limp (10 / 350μs) 0 5KA/wire 2KA/wire 0 5KA/wire 2KA/wire
    Protection voltage Up ( line-to-line) 40V 60V
    Protection voltage Up   line to ground 600V 600V

     

    Temperature range -40℃~+80℃
    Relative humidity 10%~95%
    External dimensions (length x width x height) 105mm X 7mm X 83mm
    Connection Screw wiring
       
    Maximum cross-sectional area of the wire 2.5mm
    Cross section area of guide rail grounding wire 4~6mm
    Installation method DN35mm Rail

    Outline dimension diagram

    PHL-S.Ex (1).png

    Functional schematic diagram

    PHL-S.Ex (2).png

    Naming method

    PHL-S.Ex (3).png

    Typical applications

    PHL-S.Ex (4).png

     

    Security certificate

    Lightning protection performance test
     
    Shanghai Lightning Protection Products Testing Center
    Certification standard:   GB/T 18802.21(IEC 61643-21)
    National Industrial Automation Instrument Product Quality Supervision and Inspection Center
    "Certification standard:  GB/T 20438.1(IEC 61508-1)
                                           GB/T 20438.2(IEC 61508-2)"
     
    Wiring
    (1)Instrument wiring is 2.5 screw terminal;
    (2) The terminal can be connected with multi-strand copper wire with cross-sectional area of 0.2~2.5mm2 or single-strand copper wire with cross-sectional area of 0.2~4mm2 ;
    (3)The length of wire stripping is about 5-8mm, which is locked by screws.
    PHL-S.Ex (5).png
    Installation

    The PHL-S.Ex series universal model adopts the DIN35mm guide rail installation method, and the steps are as follows:

    ⑴Clamp the upper metal at the bottom of the instrument on the DIN rail;
    ⑵Push the metal part at the bottom of the instrument into the guide rail;
    ⑶Suggest using copper or steel rails.

    PHL-S.Ex (6).png

    Disassembly

    (1)Insert a screwdriver (blade width ≤ 3.5 mm) into the groove at the bottom of the instrument panel;
    (2) Push the screwdriver upwards to pry up the metal latch;
    (3)Pull the instrument down and out of the guide rail.

    PHL-S.Ex (7).png

    Maintenance

    (1) When using SPD, there must be reliable grounding;
    (2) Before the SDP is electrified and debugged, it is necessary to check again whether the connection between the input and output terminals is correct;

    (3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the work is abnormal and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline in time;
    (4) Within one year from the date of delivery, any product quality problems during normal use shall be repaired by Beijing Pinghe free of charge.