PHL-T series

Other

Products Categories
Featured Products

PHL-T series

PHL-T series SPD is mainly used to protect transmitters, switches, frequency signals, communication equipment, thermal resistors, thermocouples and other field devices connected in two-wire, three-wire and four-wire systems, as well as control room I/O, DCS, PLC and other devices, so as to prevent them from being damaged by lightning surge impulse voltage or operating overvoltage.

    Features

    The main features are:

    1. With failure window diagnosis function (optional)

    2. 12.4mm ultra-thin, compatible with dual-channel signal transmission, saving space;

    3. High bandwidth and low insertion loss, suitable for all kinds of signals;

    Technical data

    Parameter PHL-T5-L2-EX
    PHL-T5-L3-EX
    PHL-T5-L4-EX
    PHL-T5-G2-EX
    PHL-T5-G4-EX
    PHL-T24-L2-EX
    PHL-T24-L3-EX
    PHL-T24-L4-EX
    PHL-T24-G2-EX
    PHL-T24-G4-EX
    Rated operational voltage 5VCD 5VCD 24VDC 24VDC
    Maximum operating voltage Uc 6VDC 6VDC 32VDC 32VDC
    Rated operating current  IL 600mA 600mA 600mA 600mA
    Via resistance 1Ω/线 1Ω/wire 1Ω/wire 1Ω/wire
    Bandwidth (-0.5dB) 10MHZ 10MHZ 10MHZ 10MHZ
    Response time 1ns 1ns 1ns 1ns
    Leakage current <10uA <1uA <10uA <10uA
    Nominal discharge current In (8 / 20μs) 10kA/wire 10kA/wire 10kA/wire 10kA/wire
    The maximum discharge current  Imax (8 / 20μs) 20kA/wire 20kA/wire 20kA/wire 20kA/wire
    Lightning surge current limp (10 / 350μs) 2.5kA/wire 2.5kA/wire 2.5kA/wire 2.5kA/wire
    Protection voltage Up       line-to-line 40V 40V 60V 60V
    Protection voltage Up   line to ground 600V 40V 600V 60V

     

    Temperature range -40℃~+80℃
    Relative humidity 10%~95%
    External dimensions (length x width x height) 90.0mm×12.4mm×77.5mm
    Connection Screw wiring
    Maximum cross-sectional area of the wire 2.5mm
    Cross section area of guide rail grounding wire 4~6mm
    Installation method DN35mm Rail

     

    Outline dimension diagram

    PHL-T24 .png

    Failure window diagnosis function

    PHL-T24(1).png

    Security certificate

    Lightning protection performance test
    Shanghai Lightning Protection Products Testing Center
    Certification standard: GB/T 18802.21(IEC 61643-21)
    Functional safety level: SIL3
     
    National Industrial Automation Instrument Product Quality Supervision and Inspection Center
    "Certification standard:GB/T 20438.1(IEC 61508-1)
    GB/T 20438.2(IEC 61508-2)"
    Explosion-proof certification mark:Ex ia IIC T4〜T6 Ga
     
    China national quality supervision and test centre for explosion protected electrical products (CQST)
    "Certification standard:GB 3836.1(equals to IEC 60079-0)
    GB 3836.4(equals to IEC 60079--11)"
    Explosion-proof parameters: (see explosion-proof certificate for details)
     
    Functional schematic diagram
    PHL-T24(2).png
    Typical applications
    PHL-T24(7).png
    Naming method
    PHL-T24(3).png
     Wiring
    (1)Instrument wiring is 2.5 screw terminal;
    (2) The terminal can be connected with multi-strand copper wire with cross-sectional area of 0.2~2.5mm2 or single-strand copper wire with cross-sectional area of 0.2~4mm2 ;
    (3)The length of wire stripping is about 5-8mm, which is locked by screws.
    PHL-T24(8).png
    Installation

    The PHL-T series universal model adopts the DIN35mm guide rail installation method, and the steps are as follows:

    ⑴Clamp the upper metal at the bottom of the instrument on the DIN rail;
    ⑵Push the metal part at the bottom of the instrument into the guide rail;
    ⑶Suggest using copper or steel rails.

    PHL-T24(10).png

    Disassembly

    PHL-T24(9).png

    Maintenance

    (1) When using SPD, there must be reliable grounding;
    (2) Before the SDP is electrified and debugged, it is necessary to check again whether the connection between the input and output terminals is correct;

    (3) The products have undergone strict inspection and quality control before leaving the factory. If you find that the work is abnormal and suspect that the internal module is faulty, please contact the nearest agent or directly contact the technical support hotline in time;
    (4) Within one year from the date of delivery, any product quality problems during normal use shall be repaired by Beijing Pinghe free of charge.