- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
PHL-T24-L2
Product overview
This is an intrinsic safety surge protection device for 24 V voltage systems, which has the following characteristics:
12.4mm ultra-thin design: The design is very compact, suitable for places with limited space, and can be easily installed in control cabinets or other equipment.
The surge protection module is hot swappable, which eliminates the need to shut down the system during maintenance and replacement of the protection module, improving the convenience and safety of operation.
Single use detection: The surge protection module can be tested separately, which helps to quickly identify and solve problems, ensuring the continuous operation of the system.
Suitable for various signal circuits: can be applied to various signal circuits such as AI (analog input), AO (analog output), DI (digital input), DO (digital output), RS232, etc., providing effective surge protection for these circuits.
Grounding through DIN35 metal guide rail: Grounding through metal guide rail ensures the reliability of equipment grounding, further improving the stability and safety of the system.
This is an intrinsic safety surge protection device for 24 V voltage systems, which has the following characteristics:
12.4mm ultra-thin design: The design is very compact, suitable for places with limited space, and can be easily installed in control cabinets or other equipment.
The surge protection module is hot swappable, which eliminates the need to shut down the system during maintenance and replacement of the protection module, improving the convenience and safety of operation.
Single use detection: The surge protection module can be tested separately, which helps to quickly identify and solve problems, ensuring the continuous operation of the system.
Suitable for various signal circuits: can be applied to various signal circuits such as AI (analog input), AO (analog output), DI (digital input), DO (digital output), RS232, etc., providing effective surge protection for these circuits.
Grounding through DIN35 metal guide rail: Grounding through metal guide rail ensures the reliability of equipment grounding, further improving the stability and safety of the system.
SPECIFICATIONS
Technical data |
Two-wire |
Three-wire |
Four-wire |
Rated operating voltage Un |
24V |
24V |
24V |
Maximum operating voltage Uc |
32V |
32V |
32V |
Nominal operating current IL |
1A |
1A |
1A |
Nominal discharge current In (8 / 20μs) |
10kA |
10kA |
10kA |
Maximum discharge current (8 / 20μs) |
20kA |
20kA |
20kA |
Lightning surge current limp (10 / 350μs) |
2.5kA |
2.5kA |
2.5kA |
Total lightning surge current (10 / 350μs) |
5kA |
7.5kA |
10kA |
Protection voltage Up (8 / 20μs) line-to-line / line to ground |
60V/600V |
60V/600V |
60V/600V |
Protection voltage Up (1KV / μs) line to line / line to ground |
40V/600V |
40V/600V |
40V/600V |
Bandwidth (-0.5dB) |
10MHz |
10MHz |
10MHz |
Response time |
1ns |
1ns |
1ns |
Series resistance (per line) |
1Ω |
1Ω |
1Ω |
Leakage current |
<1μA |
<1μA |
<1μA |
Degrees of protection provided by enclosure (in line with IEC 60529) |
IP 20 |
IP 20 |
IP 20 |
Housing material / Flame retardant grade (the UL94) |
PC/V0 |
PC/V0 |
PC/V0 |
Test standard |
GB/T 18802.21 / IEC61643-21 |
GB/T 18802.21 / IEC61643-21 |
GB/T 18802.21 / IEC61643-21 |
Working temperature range |
—40 ℃ ~ +80 ℃ |
—40 ℃ ~ +80 ℃ |
—40 ℃ ~ +80 ℃ |