Get Instant Quote
Leave Your Message
SPD backup protector T1 series

Other

Products Categories
Featured Products

SPD backup protector T1 series

SPD backup protector T1 series

    Product overview

    According to GB18802.1, GB50057 and Q/THQBOO1-2013 standards, the front end of SPD loop must be connected in series with overcurrent protection appliances required by the surge protector manufacturer.
    Because the current fuse and miniature circuit breaker can't coordinate with SPD, when the power supply is abnormal or SPD deteriorates and fails, the fire and equipment are damaged by lightning, which has seriously affected the normal operation of production!
    At present, a large number of miniature circuit breakers used in conjunction with SPD cannot be matched in the following four points:
    1.The lightning current shock is very easy to damage-the lightning protection fails;
    2.High residual voltage of lightning impulse current-the reliability of lightning protection of equipment is reduced;
    3.The power frequency free-wheeling does not trip-the power supply is abnormal and SPD is on fire;
    4.The lightning impact trips by mistake-the lightning protection fails.
    In view of the current situation that there is no SPD-specific supporting overcurrent protection device in lightning protection industry, after three years of research and development and more than one year of various environmental simulation experiments in the laboratory, it is proved that SPD backup protector (SCB)
    1.SPD power frequency freewheeling trip value 4A
    2.Non-trip impulse current is greater than 40kA(8/20);
    3.Lightning impulse residual depression. Completely solve the current situation that SPD has no special over-current protection appliances; The direct effect of cooperation between SCB and SPD is to ensure that SPD does not catch fire and lightning current impact does not trip.
     
    Function and scope of application
     
    SPD special external disconnector is connected in series on SPD loop, and internal current sorting channel device is used to realize power frequency small current quick break; High current lightning impact does not trip. Achieve the function of power frequency small current SPD fire protection and lightning impact SPD continuous protection; SCB products are only used for SPD loop overcurrent protection, or backup current protection. Please do not use them in other occasions.
     
     
    Product features
    1. Parameter-controlled tripping mechanism, which can realize selective breaking through current;
    2. The residual voltage of impulse current is low, which can be comparable to that of fuse;
    3. High-energy contact, with long service life;
    4. Micro-broken shape, small volume, convenient for power failure to detect SPD;
    5.Complete specifications, meeting the requirements of supporting SPD at T1, T2 and T3 levels.
    6.35mm clamp rail installation meets the installation needs all over the world.
    后备2.png
     
    Model naming rules
    后备1.png
     
    Main technical parameters
     
    Specifications  PHSCB-15 PHSCB-25
    Non-tripping impulse current Ie ≤15kA(10/350)us) ≤25kA(10/350)us)
    Non-tripping impulse current tolerance 60kA(8/20)16 times
    15kA(10/350)2 times
    80kA(8/20)16 times
    25kA(10/350)2 times
    Rated operating voltage  Ue 230VAC
    Rated isolation voltage Ui 400VAC
    Current trip value  Id 3土1A
    Operating short-circuit capability Ics 65kA/100kA
    Short-circuit current breaking time   Tcs ≤40ms
    Load current breaking time  To ≤50ms
    Mechanical life >1000times
    Electrical life >1000times
    Enclosure protection grade IP20
    Wire pressing screw M5
    Minimum area of connecting cable 2 5mm2/flexible
    Maximum area of connecting cable 25mm2/flexible
    Maximum allowable working current of remote signalling contact 2A/250VAC Normally closed or normally open (default to normally closed)
    Shell material PA 66 UL94V-O
    Outline dimension                   Small shell 90x72x69mm         large  shell 90x144x69mm
    Relationship between protection action and ambient temperature                     No relation between-25℃ and-60℃
    Storage environment      temperature -40°C-75°C      relative humidity <95% (25°C  Below)
    Working environment temperature -40°C-75°C      relative humidity <95% (25°C  Below)
    Shell color           Shell white     Handle gray
    Installing  guide rail EN60715 (35mm)

    Installation wiring schematic diagram

    后备3.png

    Application case

    后备4.png

    Dimensional drawing

    Overall dimension drawing of 36mm large shell

    T1.jpg

    Overall dimension drawing of 18mm small shell

    T1(1).jpg