- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
Isolator Conversion motherboard PHED-16AIO-D
Analog Input/Output Rail Conversion Board PHED-16AIO-D
Number of channels: 16 (dual channel isolation barrier)
Signal type: dual line analog (current) input and current output, three terminal isolation
Supporting safety barrier: Pinghe series dual channel analog safety barrier, please refer to the safety barrier manual for details
Supporting isolator: Pinghe series dual channel analog isolator, see isolator manual for details
Loop current: LED current indication online test hole
Installation form: rail installation or M4.8 self tapping or M4 screw installation
Supporting card components:
Base: MB74*
Card: AI713/AO713
Power supply:
This product is designed for redundant power supply and comes with a power loss alarm output
Attention: The safety barrier isolator does not have the ability to supply power to conventional three wire transmitters. In special circumstances, it can be connected using a four wire system.
Special note:
1. The brightness of the circuit LED can roughly indicate the magnitude of the circuit current;
2. Using a multimeter to short-circuit the current range of this circuit test hole can accurately measure the inner current without affecting the circuit operation;
When the circuit LED fails and opens, a spare LED can be inserted into the test hole for repair;
Order model |
PHED-16AIO-D |
describe |
Analog input-output conversion board |
Technical parameters | |
Channel |
16 |
Number of isolation barriers |
8 dual channels |
Internal power supply voltage |
22-30VDC redundant power supply |
Power loss alarm output |
normally closed |
Internal circuit current indication |
LED brightness, non rewiring test hole |
Maximum current of on-site side channel |
25mA |
Internal connection type |
D-SUB37P |
On site side connection type |
screw |
Terminal crimping specifications |
0.3~2.5(mm2) |
signal type |
2-wire and four wire signal systems,Temperature signal, current output |
Isolator output signal |
4-20mA |
operation temperature |
-30˚C~+55˚C |
storage temperature |
-40˚C~+70˚C |
Dimensions (length x width x height) |
168x112x60mm |
Installation size |
M4.8 self tapping or M4 screw * 2 159mm |
attachment | |
Power insurance |
Fang Insurance 2A |
Matching Cable | |
Order model |
Self equipped central control system |