- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
Isolator Conversion motherboard PHFD-16DI
Digital Input Isolation Conversion Board PHFD-16DI
Number of channels: 16
Signal type: Single line digital quantity (switch, proximity switch NAMUR) input, three terminal isolation
Supporting isolation barrier: Pinghe single channel digital input rail grid (12.8mm)
Loop current: LED current indication online test hole
Installation form: M4.8 self tapping or M4 screw fixation
Supporting card components:
S7-300PLC: 6ES7 321-1BH02/1BH10/650-8DK70, etc.
Common configurations:
Single channel digital input isolation barrier: Pinghe single channel digital input rail grid (12.8mm)
Power supply and DB port power settings:
This product is designed for redundant power supply and comes with a power loss alarm output
The DB port contains a 4-core power cord for supplying power to the PLC module. These power supplies are controlled by short-circuit caps set by the power output, with each short-circuit cap corresponding to a wire, as shown in the upper right figure. Before power transmission, settings should be made as needed.
Special note:
1. The brightness of the circuit LED can roughly indicate the magnitude of the circuit current;
2. Using a multimeter to short-circuit the current range of this circuit test hole can accurately measure the inner current without affecting the circuit operation;
When the circuit LED fails and opens, a spare LED can be inserted into the test hole for repair;
Parameter:
Order model |
PHFD-16DI |
describe |
Digital input isolation conversion board |
Technical parameters |
|
Channel |
sixteen |
Number of isolation barriers |
16 single channel |
Internal power supply voltage |
22-30VDC redundant power supply |
Power loss alarm output |
normally closed |
Internal circuit current indication |
LED brightness, non rewiring test hole |
Inner logic |
High/Low Effective Optional (K1) |
Internal connection type |
D-SUB25PF |
On site side connection type |
screw |
Terminal crimping specifications |
0.3~2.5(mm2) |
signal type |
Dry contact, NAMUR switch |
operation temperature |
-30˚C~+55˚C |
storage temperature |
-40˚C~+70˚C |
Dimensions (length x width x height) |
232X112*60mm |
Installation size |
M4.8 self tapping or M4 screw 223mm |
attachment |
|
Power insurance |
Fang Insurance 2A |
Matching Cable |
|
Order model |
FL-20D-22A20-Y-Z-Xm |
Note: Y-PLC side interface model Z-card and signal type X-length |
Note: Y-PLC side interface model Z-card and signal type X-length |
