Get Instant Quote
Leave Your Message
PHC-22HD-1111

H Series Backplane Mounting Isolated Safety Barriers

Products Categories
Featured Products

PHC-22HD-1111

4~20mA input/4~20mA output
H Serie Backplane Mounting Isolated Safety Barriers
2 inputs 2 outputs

    Overview

    H serie backplane mounting isolated safety barriers at operating side: PHC-22HD-1111, dual input

    and dual output with analog signal.

    The safety barrier can transmit the 4~20mA signal from safe area to the dangerous area, to drive the valve positioner, electric/gas converters and other actuators to work.

    This product needs independent power supply.

    Terminal isolation between power supply, input and output.

     

    Specifications

    Supply voltage 20~35VDC, power consumption about 1.2W (when 24 VDC, output 20mA)
    Input signal 4~20mA (HART)
    Output signal 4~20mA (HART)
    Allowable output load capacity 0~800 Ω
    Output accuracy 0.1%F.S (Typical value: 0.05%F.S)
    Temperature drift 0.005%F.S/℃
    Channel number of input and output 2 input 2 output
    Applicable field equipments Valve positioner, electric/pneumatic converter
    Temperature parameters Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe terminal (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    External dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
    Functional safety certification SIL2 according to IEC 61508 EN 61511 standards
    Certification body CQST (China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 2-1) Um=250V Uo=28V Io=93mA Po=0.65W Co=0.083μF Lo=4.2mH
    Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
    MTBF ≤100000h

     

    Wiring diagram

    PHC-22HD-114b1