- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
PHD-11HD-21
Overview
Isolated safety barrier at detection side: PHD-11HD-21, analog input and output, single input and single output.
The isolated barrier can isolate and transmit the 4~20mA signal or DC 4~20 mA signal generated by the transmitter in the dangerous area to the safe area. When the transmitter is two-wire or three-wire system, the safety barrier provides power for the transmitter.
This product needs independent power supply.
This product supports HART signal and disconnection alarm.
Main technical parameters |
|
Number of channels: |
one input and one output |
Power supply: |
|
Power supply voltage: |
20~35V DC, power consumption of about 1.5W (24V DC, output 20mA) |
Power protection: |
power reverse protection |
Hazardous side input: |
|
Input signal: |
2-wire, 3-wire or current source 4-20mA (HART). |
Distribution voltage: |
open-circuit voltage ≤28V, output voltage ≥15.5V when the circuit is 20mA. |
Safety side output: |
|
Output signal: |
4~20mA (HART) |
Allowable Output Load Capacity: |
0~500Ω (Customizable) |
Output accuracy: |
0.1%F.S |
Temperature Drift: |
0.005%F.S/°C |
LED indicator: |
Green—power indication |
Response time: |
2ms to 90% of final value |
Insulation strength: |
intrinsically safe end and non-intrinsically safe end (≥3000V AC/min); power supply and non-intrinsically safe end between (≥1500V AC/min) |
Insulation resistance: |
≥100MΩ (input/output/power supply between) |
Electromagnetic compatibility: |
in line with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
Applicable field devices: |
2-wire transmitter, 3-wire transmitter, current source signal. |
Installation site: |
can be connected with ⅡA, ⅡB, ⅡC hazardous gases, intrinsically safe instruments in Zone 0. |