Get Instant Quote
Leave Your Message
PHD-11HZ-*1

H Series Backplane Mounting Isolated Safety Barriers

Products Categories
Featured Products

PHD-11HZ-*1

RTD input/4~20mA output (configurable)
H Serie Backplane Mounting Isolated Safety Barriers
1 input 1 output

    Overview

    Isolated safety barrier: PHD-11HZ-*1, RTD signal input, one input and one output.

    The isolated safety barrier can convert the RTD input signal in hazardous area to 4~20mA signal output and transmit it to the safe area. The circuit is equipped with single RTD signal input and DC signal output.

    The output 4~20mA signal, can be intelligently configured. The actual range of RTD can be set by computer.

    PHD-11HZ-*1, "*" indicates the input type of RTD, please use the code to indicate. This product needs independent power supply.

     

    Input signal types and measurement range
    Code RTD model Measurement range Minimum range Conversion accuracy
    1 G53 -50~150℃ 20 0.2/0.1%
    2 G50 -50~150℃ 20 0.2/0.1%
    4 Pt100 -200~850℃ 20 0.2/0.1%
    6 Pt1000 -200~850℃ 20 0.2/0.1%
    7 Ni1000 -60~250℃ 20 0.2/0.1%

    Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, the output channel 1 is 4~20mA, the power supply is 20~35VDC, the model is PHD-11HZ-41(0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer.

     

    Specifications

    Supply voltage 20~35VDC, power consumption<1.2W (when power supply 24VDC, output 20mA)
    Input signal Two-wire or three-wire RTD
    Output signal 4~20mA
    Signal and measurement range Signal range: corresponding to the measurement range of RTD
    Measurement range: When make an order, the user shall make the configuration by himself, which shall be
    indicated in the tail number or extra explained
    Allowable output load capacity 0~500Ω (customizable)
    Alarm indication L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm
    Channel number of input and output 1 input 1 output
    Applicable field equipments 2-wire or 3-wire RTD (G53, Cu50, Pt100, Pt1000, Ni1000)
    Output accuracy 0.1%F.S (Typical value: 0.05%F.S)
    Temperature drift 0.005%F.S/℃
    Temperature parameter Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min);between power supply and non-intrinsically safe side (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    External dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 1-3,2-3) Um=250V Uo=8.4V Io=31mA Po=65.1mW Co=4.8μF Lo=20mH
    Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
    MTBF ≤100000h

     

    Wiring diagram