- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
0102030405
PHD-12HD-211
Overview
Isolated safety barrier at detection side: PHD-12HD-211, analog input and output, single input and dual outputs.
The isolated barrier can isolate and transmit the 4~20mA signal or DC 4~20 mA signal generated by the transmitter in the hazardous area to the safe area. When the transmitter is two-wire or three-wire system, the safety barrier provides power for the transmitter.
This product needs independent power supply.
This product supports HART signal and disconnection alarm.
| Supply voltage | 20~35VDC, power consumption<2W (when supply power 24VDC, transmitter input, output 20mA) |
Distribution voltage |
When the circuit output is 20mA, the provided voltage is≥15.5V |
| Input signal | Two-wire or three-wire transmitter or current source signal (HART) |
| Output signal | 4~20mA (HART) |
| Allowable output load capacity | 0~500Ω (customizable) |
| Output accuracy | 0.1%F.S (Typical value: 0.05% F.S) |
| Temperature drift | 0.005% F.S/℃ |
| Number of input and output | 1 input 2 outputs |
| Applicable field equipments | 2-wire, 3-wire transmitter and current source signal, this product is suitable for ABB, Fisher, Rosemount, |
| Honeywell 11, as well as 3351, EJA, SIEMENS and other products with imported technology | |
| Temperature parameter | Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Insulation strength | Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); |
| between power supply and non-intrinsically safe side (≥1500VAC/min) | |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Dimensions | Thickness 15.8mm * width 104.8mm * high 116.1mm |
| Electromagnetic compatibility | According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
| Explosion-proof mark | [Exia Ga]IIC, [Exia Da]IIIC |
| Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
| Certified parameters (between terminals 2-3、2-1) |
Um:250VAC/DC,Uo=28VDC,Io=93mA,
Po=0.65W,Co=0.083μF,Lo=4.2mH
|
| Certified parameters (between terminals 3-1) |
Um:250VAC/DC,Uo=7.2VDC,Io=--mA,
Po=--W,Co=12μF,Lo=--mH
|
| Installation site requirements | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
| MTBF | ≤100000h |

PHD-11TC-33A-23