Get Instant Quote
Leave Your Message
PHD-11TZ-*1

Temperature input

Products Categories
Featured Products

PHD-11TZ-*1

RTD input isolated safety barrier 

1 input 1 output

Two-wire or three-wire RTD signal input/ 4~20mA output (configurable)

 

 

    Overview

    The RTD input isolation safety barrier can convert the two wire or three wire thermistor (RTD) signals in hazardous areas into 4-20mA current signals and output them to the safety zone. It can be intelligently configured, and the actual range of the thermal resistance can be set through computer software. It has the functions of wire breakage alarm and out of range alarm.

    This product requires independent power supply, with isolated power supply, input, and output terminals.

    "*" represents the input type of the thermistor, and the specific model is represented by a code (see "Input Signal Type and Range Table" for details).

     

    Input signal types and measurement range

    Code RTD model Measurement range Minimum range Conversion accuracy
    1 G53 -50~150℃ 20℃ 0.2℃/0.1%
    2 Cu50 -50~150℃ 20℃ 0.2℃/0.1%
    4 Pt100 -200~850℃ 20℃ 0.2℃/0.1%
    6 Pt1000 -200~850℃ 20℃ 0.2℃/0.1%
    7 Ni1000 -60~250℃ 20℃ 0.2℃/0.1%

    Example: when the input are 2 inputs with K-couple, temperature range is 0~1200℃, 2 outputs 4~20mA, power supply 20~35VDC, then the model should be PHD-22TT-1111 (0~1200℃).

    The measuring range can be set to the specified 0~1200℃ range by computer.

    * Bus terminal power supply, please see appendix for details.

     

    Specification

    Input in harzadous area

     

    Input signal

    Two wire or three wire thermistor signals (see "Input Signal Type and Range Table" for details)

    Input disconnection

    The default "low alarm" can be modified to "high alarm" through configuration software

    Signal range

    Corresponding measurement range of thermal resistance

    Measurement range

    Users make their own configuration when ordering, and indicate it at the tail number or otherwise.

    Safety side output:

     

    Output signal

    4~20mA

    Output load capacity

    0~500Ω(customizable)
    Optional voltage output type, load resistance RL ≥ 330kΩ

    LED indicator

    Green: Power indicator
    Low range alarm yellow light on, high range alarm red light on

    Output accuracy

    Please refer to the "Input Signal Type and Range Table" for details

    Response time

    Reaching 90% of the final value within 300ms

    Temperature drift

    0.005%F.S/℃

    Temperature parameters

    Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃

    Relative humidity

    10%~95% RH no condensation

    Dielectric strength

    Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
    between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)

    Insulation resistance

    ≥100MΩ (between input/output/power supply)

    Electromagnetic compatibility

    According to IEC 61326-1(GB/T 18268), IEC 61326-3-1

    MTBF

    100000h

    Wire requirements

    Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V

    Applicable field equipments

    Two wire or three wire thermistors
    G53, Cu50, Pt100, Pt1000, Ni1000

    Installation place

    Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC

    Intrinsically safe certification

     

    Functional safety certification

    SIL3 according to IEC 61508 standards

    Explosion proof mark

    [Ex ia Ga]lIC [Ex ia Da]lllC

    Explosion-proof standard

    GB/T3836.1-2021  GB/T3836.4-2021

    Terminals 3-2、4-2

    Um:250V AC/DC Uo=8.4V DC lo=31mA
    Po=65.1mW Co=4.8μF Lo=20mH

    Certification body

    CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

    Schematic diagram

    333lnl

    Note:
    1. PHD-11TZ - * 1 does not include output part 2
    2. The power rail function is an optional function, and users need to specify the power supply method when placing an order
    The selection of power rail connectors can refer to page 89 of the "Annex"
    3. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible
    4. When inputting a two-wire RTD, safety barrier terminals 4 and 2 must be short circuited

     

    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply +

    2035VDC

    10

    Power supply -

     

    2-wire

    3-wire

    2

    with 4 short connected

    Input-

    3

    Input+

    Input+

    4

    Input-

    Input-

    5

    Output+

    420mA

    6

    Output-

     

    phd-11tz-X1(1)wq3

     

    Product Display

    PHD-11TF-28ysk
    PHD-11TF-288tl