- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
PHD-22TZ-*1*1
Overview
| Code | RTD model | Measurement range | Minimum range | Conversion accuracy |
| 1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 2 | Cu50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 4 | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 6 | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 7 | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |
| Specifications | |
| Input in hazardous area | |
| Input signal | Two wire or three wire thermistor signals (see "Input Signal Type and Range Table" for details) |
| Input disconnection | The default "low alarm" can be modified to "high alarm" through configuration software |
| Signal range | Corresponding measurement range of thermal resistance |
| Measurement range | Users make their own configuration when ordering, and indicate it at the tail number or otherwise. |
| Safety side output: | |
| Output signal | 4~20mA |
| Output load capacity | 0~500Ω(customizable) Optional voltage output type, load resistance RL ≥ 330kΩ |
| Supply Voltage | 20-35VDC |
| Power consumption | ≤ 90mA ( when 24VDC power supply, 20mA output) |
| LED indicator |
Green: Power indicator
Low range alarm yellow light on, high range alarm red light on
|
| Output accuracy | Please refer to the "Input Signal Type and Range Table" for details |
| Response time | Reaching 90% of the final value within 300ms |
| Temperature drift | 0.005%F.S/℃ |
| Temperature parameters |
Working temperature: -20℃~+60℃ storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| MTBF | 100000h |
| Wire requirements | Cross section ≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Two wire or three wire thermistors G53, Cu50, Pt100, Pt1000, Ni1000 |
| Installation place | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
Safety certification
Functional safety certification |
SIL2 according to IEC 61508 standards |
Explosion-proof mark |
[Ex ia Ga] IIC [Ex ia Da] ⅢC |
Explosion-proof standard |
GB/ T 3836.1-2021 GB/T 3836.4-2021 |
Terminals 1-3、2-3、4-6、5-6 |
Um:250V AC/DC Uo=8.4V DC Io=31mA |
Certification body: |
CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |

Note: 1. The power rail function is an optional function, and users need to specify the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"
2. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible
3. When inputting a two-wire RTD, safety barrier terminals 5 and 6(2 and 3) must be short circuited