- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
0102030405
PHD-12TZ-*11
Overview
Isolated safety barrier: PHD-12TZ-*11, RTD signal input, single input and dual output.
The isolated safety barrier can convert the RTD input signal in hazardous area to 4-20mA signal output and transmit it to the safe area. The circuit is equipped with single RTD signal input and DC dual output.
The output 4-20mA signal, can be intelligently configured. The actual range of RTD can be set by computer.
PHD-12TZ-*11, "*" indicates the input type of RTD, please use the code to indicate.
This product needs an external 20~35VDC power supply.
Input signal types and measurement range
| Code | RTD model | Measurement range | Minimum range | Conversion accuracy |
| 1 | G53 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 2 | Cu50 | -50~150℃ | 20℃ | 0.2℃/0.1% |
| 4 | Pt100 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 6 | Pt1000 | -200~850℃ | 20℃ | 0.2℃/0.1% |
| 7 | Ni1000 | -60~250℃ | 20℃ | 0.2℃/0.1% |
Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, with two outputs 4~20mA, power supply 20~35VDC, the model is PHD-12TZ-411 (0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer
* Bus terminal power supply, please see appendix for details.
| Specifications | |
| Supply voltage | 20~35VDC, Power consumption: When 24VDC power supply, 20mA output ≤70mA(PHD-12TZ-*11)
|
| Input signal | Two-wire or three-wire RTD |
| Output signal | 4~20mA |
| Signal and measurement range | Signal range: corresponding to the measurement range of RTD |
| Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained. | |
| Allowable output load capacity | 0~500Ω(customizable) |
| Alarm indication | L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm |
| Channel number of input and output | 1 input 2 outputs |
| Applicable field devices | 2-wire or 3-wire RTD(G53, Cu50, Pt100, Pt1000, Ni1000) |
| Output accuracy | 0.1%F.S (Typical value: 0.05%F.S) |
| Temperature drift | 0.005%F.S/℃ |
| Temperature parameters | Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| External dimensions | Thickness 12.5mm x width 108mm x high 118mm |
| Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| Functional safety certification | SIL3 according to IEC 61508 standards |
| Explosion-proof mark | [Ex ia Ga] IIC [Ex ia Da] ⅢC |
| Certification Body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
| Terminals 3-2、4-2 |
Um:250V AC/DC Uo=8.4V DC Io=31mA
Po=65.1mW Co=4.8μF Lo=20mH
|
Installation place |
Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
| MTBF | ≤100000h |

Note: 1. PHD-11TZ - * 1 does not include output part 2
2. The power rail function is an optional function, and users need to specify the power supply method when placing an order
The selection of power rail connectors can refer to page 89 of the "Annex"
3. When inputting a three wire RTD, it is necessary to ensure that the three wires are of equal length as much as possible
4. When inputting a two-wire RTD, safety barrier terminals 4 and 2 must be short circuited

PHD-11TC-33A-23