PHD-22TP-1313 /PHD-22TP-2323

Frequency Input

Products Categories
Featured Products

PHD-22TP-1313 /PHD-22TP-2323

Frequency signal input isolated safety barrier

2 inputs 2 outputs

Frequency signal  Input 

Frequency signal 1: 1 Output 

    Overview

    The frequency signal is input into the isolated safety barrier, which can realize the 1: 1 transmission of the frequency signal of the instrument in the dangerous area to the safe area, and provide the isolated power supply (12V or 24V) for the field instrument in the dangerous area. 
    This product needs independent power supply, and the power supply, input and output are isolated between each other.

    Specifications

    Input in harzadous area
    Input signal Frequency ≤ 100kHz, amplitude ≤ 12V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-1313) Frequency ≤ 100kHz, amplitude ≤ 24V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-2323)
    Distribution voltage Open circuit voltage ≤ 13V, distribution voltage ≥ 8.5V when loaded with 25mA (PHD-22TP-1313)
    Open circuit voltage ≤ 25V, distribution voltage ≥ 16V when loaded with 25mA (PHD-22TP-2323)
    Safety side output:
    Output signal Frequency quantity 1: 1 output
    Signal range Signal low-level ≤ 0.5V
    Signal high level ≥ 10V (PHD-22TP-1313)
    Signal high level ≥ 20V (PHD-22TP-2323)
    Drive current ≤ 15mA, load resistance ≥ 1k Ω
    Supply voltage 20-35VDC
    Power consumption When powered by 24VDC and output at 12V level
    ≤ 80mA (PHD-22TP-1313)
    ≤ 100mA (PHD-22TP-2323)
    LED indicator  Green: Power indicator
    Receiving and transmitting switching time  ≥20ms
    Temperature parameters Working temperature: -20℃~+60℃
    storage temperature:-40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min);
    between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
    MTBF 100000h
    Wire requirements Horizontal cutting surface ≥ 0.5mm2; Insulation strength ≥ 500V
    Applicable field equipments Frequency measuring equipment
    Installation place Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC
    Intrinsically safe certification
    Explosion proof mark [Ex ia Ga]lIC [Ex ia Da]lllC
    Explosion-proof standard GB/T3836.1-2021  GB/T3836.4-2021
    PHD-22TP-1313
    Terminals 1-3、4-6 Um:250V AC/DC Uo=17.8V DC lo=260mA
    Po=1.2W Co=0.22μF Lo=0.25mH
    Terminals 2-3、5-6 Um:250V AC/DC Uo=8V DC lo=2.5mA
    Po=5mW Co=0.59μF Lo=100mH
    PHD-22TP-2323
    Terminals 1-3、4-6 Um:250V AC/DC Uo=28V DC lo=93mA
    Po=0.65W Co=0.05μF Lo=0.56mH
    Terminals  2-3、5-6 Um:250V AC/DC Uo=8V DC lo=2.5mA
    Po=5mW Co=0.05μF Lo=100mH
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)

     

    Dimension

    PHD-11TP-1313、2323.jpg

    Schematic diagram

    PHD-11TP-1313、2323(2).jpg

    Note:

    1. The power rail function is an optional function, and users need to specify the power supply method when placing an order

    The selection of power rail connectors can refer to page 89 of the "Annex"