- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
0102030405
PHD-22TP-1313 /PHD-22TP-2323
Overview
The frequency signal is input into the isolated safety barrier, which can realize the 1: 1 transmission of the frequency signal of the instrument in the hazardous area to the safe area, and provide the isolated power supply (12V or 24V) for the field instrument in the hazardous area.
This product needs independent power supply, and the power supply, input and output are isolated between each other.
| Input in harzadous area | |
| Input signal | Frequency ≤ 100kHz, amplitude ≤ 12V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-1313) Frequency ≤ 100kHz, amplitude ≤ 24V, duty cycle ≥ 20%, high-level ≥ 4V, low-level ≤ 1V (PHD-22TP-2323) |
| Distribution voltage | Open circuit voltage ≤ 13V, distribution voltage ≥ 8.5V when loaded with 25mA (PHD-22TP-1313) |
| Open circuit voltage ≤ 25V, distribution voltage ≥ 16V when loaded with 25mA (PHD-22TP-2323) | |
| Safety side output: | |
| Output signal | Frequency 1: 1 output |
| Signal range | Signal low-level ≤ 0.5V |
| Signal high level ≥ 10V (PHD-22TP-1313) | |
| Signal high level ≥ 20V (PHD-22TP-2323) | |
| Drive current | ≤ 15mA, load resistance ≥ 1k Ω |
| Supply voltage | 20-35VDC |
| Power consumption | When powered by 24VDC and output at 12V level |
| ≤ 80mA (PHD-22TP-1313) | |
| ≤ 100mA (PHD-22TP-2323) | |
| LED indicator | Green: Power indicator |
| Receiving and transmitting switching time | ≥20ms |
| Temperature parameters | Working temperature: -20℃~+60℃ |
| storage temperature:-40℃~+80℃ | |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); |
| between power supply and non-intrinsically safe terminal (≥ 1500VAC/min) | |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Electromagnetic compatibility | According to IEC 61326-1(GB/T 18268), IEC 61326-3-1 |
| MTBF | 100000h |
| Wire requirements | Cross section ≥ 0.5mm²; Insulation strength ≥ 500V |
| Applicable field equipments | Frequency measuring equipment |
| Installation place | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
| Safety certification | |
| Explosion proof mark | [Ex ia Ga]lIC [Ex ia Da]lllC |
| Explosion-proof standard | GB/T3836.1-2021 GB/T3836.4-2021 |
| PHD-22TP-1313 | |
| Terminals 1-3、4-6 | Um:250V AC/DC Uo=14.7V DC Io=207mA |
| Po=0.76W Co=0.5μF Lo=0.56mH | |
| Terminals 2-3、5-6 | Um:250V AC/DC Uo=8V DC Io=2.5mA |
| Po=5mW Co=5.9μF Lo=100mH | |
| PHD-22TP-2323 | |
| Terminals 1-3、4-6 | Um:250V AC/DC Uo=28V DC Io=93mA |
| Po=0.65W Co=0.05μF Lo=2.4mH | |
| Terminals 2-3、5-6 | Um:250V AC/DC Uo=8V DC Io=2.5mA |
| Po=5mW Co=5.9μF Lo=100mH | |
| Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |


phd-22tp-1313-phd-22tp-2323