PHD-11TT-*1

TC input/ 4-20mA output (configurable) 1 input 1 output

Overview

^ Isolated detection end safety barrier: PHD-11TT-*1, thermocouple signal input, single input and single output, the safety barrier can realize the conversion of thermocouple signal input in dangerous area into 4-20mA signal output and transmit it to safe area. The circuit has one thermocouple input and one DC signal 4-20mA output.

^ The output 4-20mA signal can be intelligently configured, and the actual measuring range can be set by computer.

^ PHD-11TT-*1, "*" indicates the input type of thermocouple, please use code to indicate it.

This product needs an external power supply of 20~35VDC

    Product Specifications

    Supply voltage 20~35VDC, power consumption<1.2W (when power supply 24VDC, output 20mA)
    Input signal K, S, E, J, B, T, R, N, TC Signals
    Output signal 4~20mA
    Signal and measurement range Signal range: corresponding to the measuring range of TC -10~100mV
      Measurement range: When make an order, the user shall make the configuration by himself, which shall be indicated in the tail number or extra explained.
    Allowable output load capacity 0~500Ω(customizable)
    Alarm indication L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm
    Channel number of input and output 1 input 1 output
    Applicable field devices K, S, E, J, B, T, R, N TC sensors
    Output accuracy 0.1%F.S (Typical value: 0.05%F.S)
    Cold junction compensation ±1℃ (Compensation range -20℃-+60℃)
    Temperature drift 0.005%F.S/℃
    Temperature parameters Working temperature: -20℃~+60℃, storage temperature:-40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥ 3000VAC/min); between power supply and non-intrinsically safe terminal (≥ 1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    External dimensions Thickness 12.5mm x width 108mm x high 118mm
    Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC
    Certification Body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 3-4)  
    Installation site Requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
    MTBF ≤100000h


    Input signal types and measurement range

    Input signal types and measurement range

    Code

    TC model

    Measurement range

    Minimum range

    Conversion accuracy

    1

    K

    -200~1370℃

    50℃

    0.5℃/0.1%

    2

    S

    -50~1760℃

    500℃

    1.5℃/0.1%

    3

    E

    -140~1000℃

    50℃

    0.5℃/0.1%

    4

    J

    -160~1200℃

    50℃

    0.5℃/0.1%

    5

    B

    250~1800℃

    500℃

    1.5℃/0.1%

    6

    T

    -200~400℃

    50℃

    0.5℃/0.1%

    7

    R

    -50~1760℃

    500℃

    1.5℃/0.1%

    8

    N

    -200~1300℃

    50℃

    0.5℃/0.1%

    Example: when the input is with K-couple, temperature range is 0~1200℃, output 4~20mA, power supply 20~35VDC, then the model should be PHD-11TT-11 (0 ~ 1200℃).
    The measuring range can be set to the specified 0 ~ 1200℃ range by computer 
    * Bus terminal power supply, see appendix for details.

    Wiring diagram

    phd11ttX1rx3
    Terminal assignments and dimensions

    Terminal

    Terminal assignments

    9

    Power supply + 20~35VDC

    10

    Power supply -

    3

    Input+ TC

    4

    Input-

    5

    Output+ 4~20mA

    6

    Output-
    phd11ttX1-17qe