Get Instant Quote
Leave Your Message
PHD-12HZ-*11

H Series Backplane Mounting Isolated Safety Barriers

Products Categories
Featured Products

PHD-12HZ-*11

RTD input/4~20mA output (configurable)
H Serie Backplane Mounting Isolated Safety Barriers
1 input 2 outputs

    Overview

    Isolated safety barrier: PHD-12HZ-*1, RTD signal input, one input and dual output.

    The isolated safety barrier can convert the RTD input signal in hazardous area to 4~20mA signal output and transmit it to the safe area. The circuit is equipped with single RTD signal input and DC signal output.

    The output 4~20mA signal, can be intelligently configured. The actual range of RTD can be set by computer.

    PHD-12HZ-*1, "*" indicates the input type of RTD, please use the code to indicate. This product needs independent power supply.

    heading-type-1

     

    Input signal types and measurement range
    Code RTD model Measurement range Minimum range Conversion accuracy
    1 G53 -50~150℃ 20 0.2/0.1%
    2 G50 -50~150℃ 20 0.2/0.1%
    4 Pt100 -200~850℃ 20 0.2/0.1%
    6 Pt1000 -200~850℃ 20 0.2/0.1%
    7 Ni1000 -60~250℃ 20 0.2/0.1%

    Example: Isolated safety barrier Pt100 input, temperature range 0~400℃, dual output  4~20mA, the power supply is 20~35VDC, the model is PHD-12HZ-411:(0~400℃), the measurement range can be set to the specified range of 0~400℃ by computer.

     

    Specifications

    Supply voltage 20~35VDC, power consumption<1.8W (when power supply 24VDC, output 20mA)
    Input signal Two-wire or three-wire RTD
    Output signal 4~20mA
    Signal and measurement range Signal range: corresponding to the measurement range of RTD
    Measurement range: When make an order, the user shall make the configuration by himself, which shall be
    indicated in the tail number or extra explained
    Allowable output load capacity 0~500Ω (customizable)
    Alarm indication L1 light is on at low-measurement range alarm; L2 light is on at high-measurement range alarm
    Channel number of input and output 1 input 2 output
    Applicable field equipments 2-wire or 3-wire RTD (G53, Cu50, Pt100, Pt1000, Ni1000)
    Output accuracy 0.1%F.S (Typical value: 0.05%F.S)
    Temperature drift 0.005%F.S/℃
    Temperature parameter Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃
    Relative humidity 10%~95% RH no condensation
    Dielectric strength Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min);between power supply and non-intrinsically safe side (≥1500VAC/min)
    Insulation resistance ≥100MΩ (between input/output/power supply)
    External dimensions Thickness 15.8mm * width 104.8mm * high 116.1mm
    Electromagnetic compatibility According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1
    Explosion-proof mark [Exia Ga]IIC, [Exia Da]IIIC
    Certification body CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products)
    Certified parameters (between terminals 1-3,2-3) Um=250V Uo=8.4V Io=31mA Po=65.1mW Co=4.8μF Lo=20mH
    Installation site requirements It can be connected with instruments in 0 zone with ⅡA, ⅡB, ⅡC dangerous gas
    MTBF ≤100000h

     

    Wiring diagram

    PHD-12HZ-X1101b