- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
0102030405
PHG-11TH/PHG-12TH
Overview
The potentiometer input signal isolator can isolate and convert the potentiometer signal into a DC signal output. The conversion circuit sends the 2.5V voltage to the input potentiometer, and the potentiometer then transmits the partial pressure back to the circuit.
This product needs to be powered independently, and the power
supply, input and output terminals are isolated.
| Input | |
| Input signal | Three-wire potentiometer |
| Output | |
| Output signal | DC signal(current/voltage) |
| Load Resistance | Current load resistance ≤500Ω |
| Voltage load resistance <5mA | |
| Basic parameters | |
| Supply voltage | 20~35V DC |
| Power consumption | Current output<0.8W, voltage output<0.5W(PHG-11TH series) |
| Current output<1.3W, voltage output<0.5W(PHG-12TH series) | |
| LED indicator | Green: power indicator |
| Output accuracy | ±0.1%F.S |
| Response time | 300ms to reach 90% of the final value |
| Temperature parameters | Working temperature: -20℃ ~ +60℃, |
| Storage temperature: -40℃ ~ +80℃ | |
| Relative humidity | 10%~95% RH no condensation |
| Insulation strength | ≥2000VAC/min (input/output/power supply) |
| Insulation resistance | 100MΩ (500V DC) (between input/output/power supply) |
| Electromagnetic compatibility | GB/T 18268 (IEC 61326-1) |
| MTBF | 80000h |
| Wire requirements | Cross section≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Three-wire potentiometer |



PHD-11TC-33A-23