- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
0102030405
PHG-11TA series / PHG-12TA series
Overview
The power transmitter with AC signal input, the AC signal is input, and the DC signal is output after isolation.
This product needs to be powered independently, and the power supply,input and output terminals are isolated.
This product needs to be powered independently, and the power supply,input and output terminals are isolated.
| Specifications | |
| Input | |
| Input signal | AC signal |
| Output | |
| Output signal | DC signal |
| Load capacity | Current load resistance ≤500Ω Voltage load resistance <5mA |
| Basic parameters | |
| Supply voltage | 20~35V DC |
| Power consumption | Current output<1W, voltage output<0.7W |
| Output accuracy | 0.2%F.S |
| Response time | 1s |
| Temperature drift | 0.02%F.S/℃ |
| Temperature parameters | Working temperature: -20℃ ~ +60℃, Storage temperature: -40℃ ~ +80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Insulation strength | ≥1500VAC/min (input/output/power supply) |
| Insulation resistance | 100MΩ (500V DC) (between input/output/power supply) |
| Electromagnetic compatibility | GB/T 18268 (IEC 61326-1) |
| MTBF | 80000h |
| Wire requirements | Cross section≥ 0.5mm2; Insulation strength ≥ 500V |
| Applicable field equipments | Current source |

Note: 1. PHG-11TA series does not include the output 2 part
2. The power supply of the power rail is an optional function. Users need to
specify the power supply mode when ordering. Please refer to attachment
on page 89.


For example: one input and one output, 0~5A AC signal input, 4-20mA DC signal output,24V power supply, model should be: PHG-11TA-11
PHD-11TC-33A-23