- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
PHL-TA-15/420/1P+N PHL-TA-15/420/3P+N
Product overview
Used for first level power surge protectors with lightning protection level of A or below, suitable for installation in high-risk areas of lightning strikes, where overhead lines directly enter households
At the junction of the LPZOA and LPZl regions, as well as other areas.
Main features
1. Pre connected base for easy wiring
2. The 'module' function allows for easy insertion and removal of modules, making it easy to replace.
Technical parameters
N-PE
L-N
N-PE
L-N
Nominal operating voltage Un
230/400VAC
230/400VAC
Maximum operating voltage Uc
255VAC
420VAC
255VAC
420VAC
Protection voltage Up(ln under)
Up< l.5kV
Up<2.2kV
Up< l.5kV
Up<2.2kV
Lightning impulse current limp (l 0/350 μ s)
15kA
15kA
Cross-sectional area of connecting wire
1.5mm²-25mm² flexible wire
1.5mm²-25mm² flexible wire
Response time
<25ns
<25ns
Leakage current
<10μA
<10μA
Enclosure protection degree (according to IEC60529)
IP 20
IP 20
Enclosure material/flammable rating
UL94-V0
UL94-V0
Test standard
GB/T18802.11/IEC 61643-11
GB/T18802.11/IEC 61643-11
Applicable power system
single phase (TT system)
single phase (TT system)
Fuse or circuit breaker selection(A)
125、160
125、160
Aging thermal separation function
yes
yes
Tele-signalization function
optional
optional
RS485 communication
optional
optional
Working temperature range
-40℃+80℃
-40℃+80℃
Installation method
DIN35mm rail
DIN35mm rail
Technical parameters |
N-PE |
L-N |
N-PE |
L-N |
Nominal operating voltage Un |
230/400VAC |
230/400VAC |
||
Maximum operating voltage Uc |
255VAC |
420VAC |
255VAC |
420VAC |
Protection voltage Up(ln under) |
Up< l.5kV |
Up<2.2kV |
Up< l.5kV |
Up<2.2kV |
Lightning impulse current limp (l 0/350 μ s) |
15kA |
15kA |
||
Cross-sectional area of connecting wire |
1.5mm²-25mm² flexible wire |
1.5mm²-25mm² flexible wire |
||
Response time |
<25ns |
<25ns |
||
Leakage current |
<10μA |
<10μA |
||
Enclosure protection degree (according to IEC60529) |
IP 20 |
IP 20 |
||
Enclosure material/flammable rating |
UL94-V0 |
UL94-V0 |
||
Test standard |
GB/T18802.11/IEC 61643-11 |
GB/T18802.11/IEC 61643-11 |
||
Applicable power system |
single phase (TT system) |
single phase (TT system) |
||
Fuse or circuit breaker selection(A) |
125、160 |
125、160 |
||
Aging thermal separation function |
yes |
yes |
||
Tele-signalization function |
optional |
optional |
||
RS485 communication |
optional |
optional |
||
Working temperature range |
-40℃+80℃ |
-40℃+80℃ |
||
Installation method |
DIN35mm rail |
DIN35mm rail |
||
Diagram
Outline dimension diagram
Connection