- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
PHL-TA-25/420/2P PHL-TA-25/420/3P PHL-TA-25/420/4P
Product overview
Used for first level power surge protectors with lightning protection level of A or below, suitable for installation in areas with high lightning strikes, where overhead lines directly enter households, and at the junction of other LPZOA and LPZl areas.
Main features
1. Module self-locking function to prevent loss of protection due to loose surfaces;
2. The module has a 'light press' function, which allows for easy insertion and removal of modules for easy replacement.
Technical parameters
Nominal operating voltage Un
230/400VAC
230/400VAC
230/400VAC
Maximum operating voltage Uc
420VAC
420VAC
420VAC
Lightning impulse current limp (10/350 μ s)
25kA
25kA
25kA
Protection voltage Up(ln under)
Up<2.5kV
Up<2.5kV
Up<2.5kV
Cross-sectional area of connecting wire
1.5mm²-25mm² flexible wire
1.5mm²-25mm² flexible wire
1.5mm²-25mm² flexible wire
Response time
<25ns
<25ns
<25ns
Leakage current
<10μA
<10μA
<10μA
Enclosure protection degree (according to IEC60529)
IP20
IP20
IP20
Enclosure material/flammable rating
UL94-V0
UL94-V0
UL94-V0
Test standard
GB/T 18802.11/IEC 61643-11
GB/T 18802.11/IEC 61643-11
GB/T 18802.11/IEC 61643-11
Applicable power system
Single phase two wire
Three phase four wire (TN-C system)
Three phase three wire (IT system)
Three phase five wire (TN-S system)
Fuse or circuit breaker selection(A)
160、250
160、250
160、250
Aging thermal separation function
yes
yes
yes
Tele-signalization function
optional
optional
optional
RS485 communication
optional
optional
optional
Working temperature range
-40℃~+80℃
-40℃~+80℃
-40℃~+80℃
Installation method
35mmDIN rail
35mmDIN rail
35mmDIN rail
Technical parameters |
|
||
Nominal operating voltage Un |
230/400VAC |
230/400VAC |
230/400VAC |
Maximum operating voltage Uc |
420VAC |
420VAC |
420VAC |
Lightning impulse current limp (10/350 μ s) |
25kA |
25kA |
25kA |
Protection voltage Up(ln under) |
Up<2.5kV |
Up<2.5kV |
Up<2.5kV |
Cross-sectional area of connecting wire |
1.5mm²-25mm² flexible wire |
1.5mm²-25mm² flexible wire |
1.5mm²-25mm² flexible wire |
Response time |
<25ns |
<25ns |
<25ns |
Leakage current |
<10μA |
<10μA |
<10μA |
Enclosure protection degree (according to IEC60529) |
IP20 |
IP20 |
IP20 |
Enclosure material/flammable rating |
UL94-V0 |
UL94-V0 |
UL94-V0 |
Test standard |
GB/T 18802.11/IEC 61643-11 |
GB/T 18802.11/IEC 61643-11 |
GB/T 18802.11/IEC 61643-11 |
Applicable power system |
Single phase two wire |
Three phase four wire (TN-C system) |
Three phase five wire (TN-S system) |
Fuse or circuit breaker selection(A) |
160、250 |
160、250 |
160、250 |
Aging thermal separation function |
yes |
yes |
yes |
Tele-signalization function |
optional |
optional |
optional |
RS485 communication |
optional |
optional |
optional |
Working temperature range |
-40℃~+80℃ |
-40℃~+80℃ |
-40℃~+80℃ |
Installation method |
35mmDIN rail |
35mmDIN rail |
35mmDIN rail |
Diagram
Outline dimension diagram
Connection
