- Isolated Safety Barriers
- Signal Isolators
- Surge Protective Devices
- Safety Relays
- Isolated Intelligent I/O Modules
- Intelligent Gateways
- Industrial Data Optical Transceivers
- Online Dew Point Analyzers
- Data Acquisition Modules
- HART data converter
- Terminal Board
PHL-TA-20/385/1P+N PHL-TA-20/385/3P+N
Product overview
A three-phase power surge protector for the second level, using a common mode protection mode of phase line to neutral line and neutral line to ground, suitable for installation in TT power supply system The branching distribution cabinet, as well as the junction of other LPZ1 and LPZ2 zones and subsequent zones.
Main characteristics
1. Pre connected base for easy wiring
2. The 'lightly press' function of the module allows for easy insertion and removal, making it easy to replace.
Technical parameters |
N-PE |
L-N |
L-N |
L-N |
N-PE |
L-N |
L-N |
L-N |
Nominal operating voltage Un |
230/400VAC |
230/400VAC |
||||||
Maximum operating voltage Uc |
255VAC |
275VAC |
385VAC |
440VAC |
255VAC |
275VAC |
385VAC |
440VAC |
Protection Up(ln under) |
Up< l.2kV |
Up<l.2kV |
Up<l.5kV |
Up<l.7kV |
Up<l.2kV |
Up<l.2kV |
Up<l.5 kV |
Up<l. 7kV |
Nominal discharge current In ( 8/20μs) |
10kA |
10kA |
||||||
Maximum discharge current lmax (8/20μs) |
20kA |
20kA |
||||||
Cross-sectional area of connecting wire |
1.5mm²-25mm² flexible wire |
1.5mm²-25mm² flexible wire |
||||||
Response time |
<25ns |
<25ns |
||||||
Leakage current |
< lOμA |
< lOμA |
||||||
Enclosure protection degree (according to IEC60529) |
IP 20 |
IP 20 |
||||||
Enclosure material/flammable rating |
UL94-VO |
UL94-VO |
||||||
Test standard |
GB/T18802.11/IEC 61643-11 |
GB/T18802.11/IEC 61643-11 |
||||||
Applicable power system |
single phase (TT system) |
three, four phase (TT system) |
||||||
Aging indicator function |
yes (indicator window turns from green to red) |
yes (indicator window turns from green to red) |
||||||
Fuse or circuit breaker selection(A) |
25、32 |
25、32 |
||||||
Aging thermal separation function |
yes |
yes |
||||||
Tele-signalization function |
optional |
optional |
||||||
RS485 communication |
optional |
optional |
||||||
Working temperature range |
-40"C~+80"C |
-40"C~+80"C |
||||||
Installation method |
DIN35mm rail |
DIN35mm rail |
||||||
Product Diagram