PHD-22HF-2727
Overview
| Supply voltage | 20~35VDC, power consumption<1.5W |
| Input signal | Switch contact or Proximity switches (NAMUR) |
| Supply voltage of sensor on site | 8V |
| Signal input characteristics | On-site input current: >2.1mA, it indication ON; On-site input current: <1.2mA, it indication OFF |
| Output in safe area | Response time: 20ms, driving capability: 250VAC/2A, 30VDC/2A under resistive load |
Output normally “Open”/“Closed” |
When the dial switch K1, K3 is at "ON" side, the relay output is "OFF" |
| When the dial switch K1, K3 is at "OFF" side, the relay output is "ON" | |
| When the dial switch K2, K4 is at "ON" side, the circuit selects indicating red light LFD alarm function | |
| LFD | On-site input current>7mA, short-circuit alarm (SC) , on-site input current<0.1mA, open-circuit alarm ( LB) |
| For switch contact input, when the disconnection detection function is required, a 22KΩ resistor must be connected parallel at both ends of the switch (Please see the switch contact II in the below wiring diagram) | |
| Number of input and output | 2 inputs 2 outputs |
| Applicable field equipments | Dry contact or NAMUR proximity switch in accordance with DIN 19234 standard |
| Temperature parameter | Working temperature: -20℃~+60℃, storage temperature: -40℃~+80℃ |
| Relative humidity | 10%~95% RH no condensation |
| Dielectric strength | Between intrinsically safe side and non-intrinsically safe side (≥3000VAC/min); between power supply and non-intrinsically safe terminal (≥1500VAC/min) |
| Insulation resistance | ≥100MΩ (between input/output/power supply) |
| Dimensions | Thickness 15.8mm * width 104.8mm * high 116.1mm |
| Electromagnetic compatibility | According to IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
| Explosion-proof mark | [Exia Ga]IIC, [Exia Da]IIIC |
| Certification standard | GB/T 3836.1-2021、GB/T 3836.4-2021 |
| Certification body | CQST(China National Quality Supervision and Test Centre for Explosion Protected Electrical Products) |
| Certified parameters (between terminals 1-2,4-5) |
Um:250VAC/DC,Uo=10.5VDC,Io=14mA,
Po=37mW,Co=2.4μF,Lo=165mH.
|
| Installation site requirements | Installed in a safe zone, it can be connected to intrinsic safety instruments in hazardous areas up to Zone 0, IIC, Zone 20, and IIIC |
| MTBF | ≤100000h |

Line Fault Detection (LFD)
Line Fault Detection (LFD) is a user-selectable switch on the top of the module and is indicated by an LED. If a line fault is detected, the line fault relay is closed and the channel output relay is disconnected. Short circuit alarm (SC) for field input current >7mA; open circuit alarm (LB) for field input current <0.1mA; switch contact input; 22kΩ resistor must be connected in parallel at both ends of the switch for line fault detection (e.g., switch contact II in the wiring diagram).